83862601 Crouzet USA, 83862601 Datasheet - Page 126

no-image

83862601

Manufacturer Part Number
83862601
Description
LMTSW 1/2NPT WOBBLE SPRING
Manufacturer
Crouzet USA
Type
Limitr
Datasheets

Specifications of 83862601

Actuator Type
Flexible
Contact Form
1 NC/NO
Current, Rating
6/3 AAC/ADC
Ip Rating
IP66
Number Of Poles
1
Number Of Positions
4
Operating Force
10 Oz. (Min.)
Operation
Momentary
Special Features
Positive Break
Temperature, Operating
-25 to +80 °C
Termination
Screw
Voltage, Rating
380/24 VAC/VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3/118
Inductive Proximity Detectors – Technical Guide
Mechanical installation advice
Protection:
Electrical installation advice
Power supply:
Connection:
Connecting more than one sensor:
Series installation:
Power
source
Power
cable
3-wire DC
detectors
2-wire detectors
AC or DC
(+)
(-)
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
a
a
(
(
(-)
(-)
+)
+)
BN
BU
BK
Detector 1
C
-
BN
BU
+
BN
BU
BN
BU
conduit
Metal
Load
BK
Detector 2
Detector 1
Detector x
BN
BU
Products and specifications subject to change without notice.
BK
Detector x
Load
Protect the cable against sharp objects or excessive heat.
Do not exert a pulling force of more than 5 kg on the cable.
The detectors are unable to withstand severe mechanical impact. The
bracket must be sufficiently rigid to resist shock and vibration.
Avoid using the detectors in a corrosive environment such as near
strong acids, etc. (e.g. Nitric Acid).
When a plastic detector is used in a chemical environment it is
advisable to first verify the plastic's resistance to the chemical.
Opposite is an example of a DC power supply for detectors using
smoothing. To ensure that the resulting voltage is less than the
maximum operating voltage of the detector, use a capacitor "C" to
remove spikes and ripples greater than ± 10 %.
Ideally, use a transformer with a secondary voltage less than your
required voltage.
Eg. 17.5 VAC from the secondary of the transformer to obtain less
than 24 VDC.
Limit the length of the cables to 100 m and the capacitance of the line
to 0.1 µF. Also separate detector cables and power cables as far as
possible.
It is possible to connect detectors in series:
- Ensure that the voltage at the terminals of each sensor is less than
- In on-state, check that there is sufficient voltage available to activate
This connection method is not possible if multivoltage sensors are
used.
With this connection method, add the voltage drop of each detector
together and deduct from the supply voltage to ensure there is
sufficient voltage to activate the load.
Note: detector 1 carries all the current for the additional detectors.
or equal to the minimum operating voltage (in off-state).
the load.