3UG4622-1AW30 SIEMENS, 3UG4622-1AW30 Datasheet - Page 35

RELAY, MONITOR, 22.5MM

3UG4622-1AW30

Manufacturer Part Number
3UG4622-1AW30
Description
RELAY, MONITOR, 22.5MM
Manufacturer
SIEMENS
Series
3UG46r
Datasheet

Specifications of 3UG4622-1AW30

Contact Configuration
SPCO
Power Consumption
4VA
Supply Voltage Max
240VAC
Contact Current Max
3A
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
230V
External Depth
86mm
Coil Frequency Max
60Hz
Coil Operating Frequency Min
50Hz
Overview
The 3UF1 8 current transformers are protection transformers and
are used for actuating overload relays. Protection transformers
are designed to ensure proportional current transfer up to a
Technical specifications
1) With or without box terminal.
2) Conductor cross-sections for box terminals, see 3TF6 8 and 3TF6 9
3) With max. conductor cross-section, a terminal cover for maintaining the
Temperatures
• Operation
• Storage/transport
Temperature changes
• Operation
• Storage/transport
Relative humidity
Air pressure
• Operation
• Storage/transport
Contaminants
• SO
• H
Vibrations
(acc. to IEC 60068-2-6)
Shock (acc. to IEC 60068-2-27)
Degree of protection (acc. to IEC 60529)
Rated insulation voltage
Rating of the insulation
(acc. to UL/CSA)
Trip class (acc. to IEC 60947-4-1)
Power loss per conducting path of the
transformers
• 3UF18 45
• 3UF18 48
• 3UF18 50
• 3UF18 52
• 3UF18 56
• 3UF18 57
• 3UF18 68-3F
• 3UF18 68-3G
Conductor cross-sections
(one or two conductors connectable)
• Terminal screw
• Solid
• Stranded
• Finely stranded without end sleeve
• Finely stranded with end sleeve
• Finely stranded with cable lug
• Stranded with cable lug
• Connecting bars
• Tightening torque
• Tightening torque
Climatic environmental conditions
Mechanical environmental conditions
Requirements acc. to IEC and DIN
contactors in the section Contactors and Contactor Assemblies.
phase spacing is required.
2
S
2
SIMOCODE 3UF Motor Management and Control Devices
°C
°C
°C/h
°C/h
%
hPa
hPa
ppm
ppm
Hz
Hz
V
V
mm
mm
mm
mm
mm
mm
mm
Nm
lb
2
2
2
2
2
2
-25 ... +60
-40 ... +85
max. 10
max. 20
15 ... 95 (indoor, acc. to IEC 60721-3, no condensation)
860 ... 1060
650 ... 1060
0.5 (relative humidity ˆ 60 %, no condensation)
0.1 (relative humidity ˆ 60 %, no condensation)
10 ... 57 (for constant amplitude 0.15 nm)
57 ... 150 (for constant acceleration 2 g)
12 shocks (half sine 15 g/11 ms)
IP20
690/1000 (type-dependent)
600
Suitable from CLASS 5 to CLASS 30
Operating range
A
12.5 ... 50
25 ... 100
32 ... 130
50 ... 200
100 ... 400
125 ... 500
160 ... 630
205 ... 820
Current transformers
on second-
ary side
M 3.5
2 ™ 1.5 ... 2.5
2 ™ 1.5 ... 2.5
--
2 ™ 1.5
--
--
--
0.8 ... 1.4
7 ... 12
on primary side
3UF18 45
for connec-
tion data
see 3RT
Contactors
multiple of the primary rated current. The 3UF18 current
transformers convert the maximum current of the corresponding
operating range into the standard signal 1 A secondary.
3UF18 48
for connec-
tion data
see 3RT
Contactors
for setting ...
to the lower limit
mW (mVA)
33 (38)
110 (120)
135 (150)
170 (190)
450 (500)
850 (940)
900 (1000)
1400 (1600)
1)
3UF18 50
for connec-
tion data
see 3RT
Contactors
1)
to the upper limit
mW (mVA)
570 (650)
1700 (1900)
2400 (2700)
2600 (2900)
6500 (7000)
13000 (15000)
17000 (19000)
22000 (25000)
3UF18 52 3UF18 56
M 8
--
--
--
--
35 ... 95
50 ... 120
20 ™ 4
10 ... 14
89 ... 124
3UF18 current transformers
Siemens LV 1 T · 2006
3UF18 57
M 10
--
--
--
--
50 ... 240
70 ... 240
25 ™ 6.30 ™
6
14 ... 24
124 ... 210
for overload protection
3
3
2)
)
)
3UF18 68-
3FA00
M 10
--
--
--
--
50 ... 240
70 ... 240
30 ™ 5
14 ... 24
124 ... 210
2)
3UF18 68-
3GA00
M 12
--
--
--
--
185 ... 240
185 ... 240
50 ™ 5
14 ... 24
124 ... 210
7/35
2)

Related parts for 3UG4622-1AW30