HIH-4602-L Honeywell Sensing and Control, HIH-4602-L Datasheet - Page 2

Humidity Sensor

HIH-4602-L

Manufacturer Part Number
HIH-4602-L
Description
Humidity Sensor
Manufacturer
Honeywell Sensing and Control
Datasheet

Specifications of HIH-4602-L

Sensing Accuracy
3.5%
Sensor Output
Voltage
Sensor Terminals
Through Hole
Supply Voltage Range
4VDC To 5.8VDC
Operating Temperature Range
-40°C To +85°C
Humidity Range
0 To 100% RH
Response Time
30s
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
HIH-4602-L-CP
Quantity:
12 800
HIH-4602-L Series
Table 1. Performance Specifications (At 5 Vdc supply and 25 ºC [77 ºF] unless otherwise noted.)
Factory Calibration Data
HIH-4602-L-CP Sensors include a calibration and data
printout. See Table 2.
Table 2. Example Data Printout
2
Parameter
Interchangeability (first order curve)
Accuracy (best fit straight line)
Hysterisis
Repeatability
Settling time
Response time (1/e in slow moving air)
Stability (at 50% RH in one year)
Voltage supply
Current supply
Output voltage temp. coefficient at 50% RH, 5 V
Voltage output (1st order curve fit)
Temperature compensation
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Specific Notes:
1. Applies to HIH-4602-L-CP only.
2. Device is calibrated at 5 Vdc and 25 ºC.
3. Non-condensing environment.
Model
Channel
Wafer
MRP
Calculated values at 5 V
Linear output for 3.5% RH
accuracy at 25 °C
Ratiometric response for
0% RH to 100% RH
V
V
Zero offset
Slope
RH
V
0% RH to 59% RH
60% RH to 100% RH
OUT
OUT
OUT
at 0% RH
at 75.3% RH
www.honeywell.com/sensing
HIH-4602-L-CP
92
030996M
337313
0.958 V
3.268 V
0.958 V
30.680 mV/%RH
(V
(V
V
SUPPLY
OUT
OUT
- zero offset)/slope
- 0.958)/0.0307
(0.1915 to 0.8130)
True RH = (sensor RH)/(1.0546-0.00216T), T in °C
Minimum
V
-40[-40]
-40[-40]
OUT
-3.5
-5
-8
4
0
= (V
SUPPLY
General Notes:
• Sensor is ratiometric to supply voltage.
• Extended exposure to >90% RH causes a reversible shift of
• Sensor is light sensitive. For best performance, shield sensor
)(0.0062(sensor RH) + 0.16), typical at 25 °C
See Figure 1.
See Figure 1.
See Figure 2.
See Figure 2.
3% RH.
from bright light.
Typical
±0.5
200
1.2
30
-4
3
Maximum
125[257]
85[185]
+3.5
500
100
5.8
70
5
8
mV/°C
% RH
% RH
% RH
% RH
% RH
% RH
°C[°F]
°C[°F]
% RH
% RH
Unit
Vdc
ms
µA
s
Specific
Note
1
2
3
3