DMPR3-E-3/4/5-36KW UA (UNITED AUTOMATION), DMPR3-E-3/4/5-36KW Datasheet

no-image

DMPR3-E-3/4/5-36KW

Manufacturer Part Number
DMPR3-E-3/4/5-36KW
Description
DUAL MODE POWER REG. 230V 36KW
Manufacturer
UA (UNITED AUTOMATION)
Datasheet

Specifications of DMPR3-E-3/4/5-36KW

Approval Bodies
CE
External Depth
232mm
External Length / Height
124mm
External Width
322mm
Fixing Centres
6mm
Fixing Centres Lxw
322x200
Input Voltage Max
400V
Mounting Type
Flange
Operating
RoHS Compliant
Control limit or over current trip
SPECIFICATIONS
Power/current Ratings:
Input Voltage:
Frequency:
Control input options:
Load Type/ Selectable (SW4)
Phase Loss Detection:
Sensor Loss Detection:
Adjustable ramp control from power up
Cable terminations:
Cable entry (power + signal):
Terminal torque settings:
Fusing
Working temperature:
Dimensions:
photo)
Fixing centres:
Weight:
Note: SAFETY WARNING - Metal parts, in particular the heatsink, may get very hot when the unit is fully operational.
Manual Control
The FC36M firing circuit has a 5Vdc output that can be used to supply the clockwise end of a 5K ohm potentiometer. The wiper is connected to the terminal marked SIG
I/P and the counterclockwise end to 0V.
Voltage control
For control using a remote dc signal the positive input should be connected to the terminal marked SIG I/P and the negative input to be connected to 0V. The input
impedance is 10K ohms for 0-5V input and 20K ohms for 0-10V input.
Current control
For current control connect a 4-20mA dc signal between terminals marked 4-20mA and 0V. This input can also be used as 1-5V dc input. The input impedance is 240
ohms.
Phase Angle control
Option 1 - the switch marked SW1 should be switched to the on position. This position connects terminals A with 5V.
Option 2 – (see Soft Starting) the switch marked SW1 can be switched to the OFF position. The OFF position isolates the inputs and disconnects terminals A from 5V.
Inputs (A and C) then require an external supply between 5 and 24V dc.
Burst Firing control
The switch marked SW1 should be switched to the OFF position and the terminal marked B should be linked to5V.
Phase Angle to Burst Firing control
The switch marked SW1 should be switched to the ON position and terminals A and B should be linked together. The firing circuit will start in phase angle mode and
switch to burst mode when the control signal ramps up to the set point. It will stay in the burst mode even if the signal drops below the set point. It will restart in phase
angle mode when the unit is switched off or reset.
Soft Start
When the FC36M is initially powered up the output is inhibited for 0.5 seconds, then the soft start is automatically enabled and the firing circuit will ramp up at a rate
determined by VR3 (0-30 seconds). The ramp time relates to full conduction, for example, if the ramp time is set to maximum (30 seconds) and the set point is 50% the
controller will ramp to the set point in 15 seconds.
INTRODUCTION
The complete enclosed three phase Dual Mode Power Regulator (DMPR3)
thyristor assembly provides control of inductive/resistive loads of up to 54kW
at 415V. The user selectable control modes, via the internal switches are
either phase angle, burst firing or a combination of the two i.e. start up in
phase angle and then continue in burst firing. The controllers also come with
frequency tracking allowing the unit to be installed in many applications
where the supply is unstable. There are a number of signal control options to
meet most industrial requirements.
All are housed in a bespoke enclosure and have easy access to internal
signal & power terminals for simple installation. With Integral semiconductor
fuses and heatsink the controller offers a solution for many application
requiring single or dual mode control.
APPLICATIONS
Suitable for furnaces, ovens, dryers, air curtains, hot plates and many other
heating and ventilation applications.
as transformers
(all internal)
3-PHASE DUAL MODE POWER CONTROLLER
INSTALLATION INSTRUCTIONS
36kW and 54kW RANGE
.
Also suitable for inductive loads such
36KW (50A); 54KW (75A) @ a typical supply of 415V RMS
400V RMS +/- 10%
30-80Hz
Signal 0 to 5V / 0 to 10V Manual
Resistive or Inductive
LED indicator flashes for 1.5sec. pulse bursts
LED indicator flashes for 1sec. pulse bursts
0-30 seconds
0-100mV dc or 0-25V dc
Phase power:
Earth:
6 x 20mm Ø cable knock-outs + 2 x 12mm Ø holes – front side only. Cable glands NOT supplied.
4.5 to 5.5Nm - Power and earth terminals only.
36kW (56ET) 54kW 80ET High-Speed Semiconductor type fuses
65°C (maximum operational)
232mm (D) x 340mm (W) 124x mm (H) – length is viewed with heatsink fins going top to bottom (see
4 x 6mm holes on centres 322mm (W) x 200mm (D)
(all models) 5.2kg
M6 nut & washer stud terminal.
M6 nut & clamp washer stud terminal.
5K Potentiometer / 4-20mA
Features
Phase Angle/Burst Fire Control or
Combination of both
Frequency Tracking 30-80Hz
Integral High Speed Fuses
Adjustable ramp control 0 to 30 seconds.
RoHS Compliant
SERIES
DMPR3
2002/95/EC
Directive
X10747

Related parts for DMPR3-E-3/4/5-36KW

DMPR3-E-3/4/5-36KW Summary of contents

Page 1

... DUAL MODE POWER CONTROLLER INSTALLATION INSTRUCTIONS INTRODUCTION The complete enclosed three phase Dual Mode Power Regulator (DMPR3) thyristor assembly provides control of inductive/resistive loads 54kW at 415V. The user selectable control modes, via the internal switches are either phase angle, burst firing or a combination of the two i.e. start up in phase angle and then continue in burst firing ...

Page 2

INSTALLATION COOLING REQUIREMENTS Heatsink temperature rating for standard stack assembly is calculated when naturally cooled. If mounted in enclosure or cabinet, adequate ventilation and/or forced air-cooling should be fitted. Thermal trips are fitted on 75A to 100A rated controllers. This ...