UM-FA-11A BANNER ENGINEERING, UM-FA-11A Datasheet - Page 15

no-image

UM-FA-11A

Manufacturer Part Number
UM-FA-11A
Description
SAFETY RELAY UM-FA-11A 22.5MM UNVRSL MODULE CNTCT/SLD ST IN 2NO & 1NC OU
Manufacturer
BANNER ENGINEERING
Datasheet
UM-FA-9A/-11A Universal Module
P/N 141249 rev. C
Category
Supply Voltage
and Current
Supply Protection
Circuitry
Overvoltage
Category
Pollution Degree
Output
Configuration
Specification
24V dc ± 10% (SELV-rated supply according to EN IEC 60950, NEC Class 2)
24V ac ± 10%, 50/60Hz (NEC Class 2-rated transformer)
Power consumption: approx. 2W/2VA
Protected against transient voltages and reverse polarity
Output relay contact voltage 1V to 150V ac/dc: Category III
Output relay contact voltage 151V to 250V ac/dc: Category II (Category III, if appropriate
overvoltage reduction is provided, as described on page 7.)
2
Model UM-FA-9A: 3 normally open (N.O.) output channels
Model UM-FA-11A: 2 normally open (N.O.) output channels and 1 normally closed (N.C.)
auxiliary output channel
Each normally open output channel is a series connection of contacts from two forced-guided
(mechanically linked) relays, K1-K2.The normally closed Aux. output channel of the UM-FA-11A
is a parallel connection of contacts from two forced-guided relays, K1-K2.
Contacts: AgNi, 5 µm gold-plated
Low Current Rating: The 5 µm gold-plated contacts allow the switching of low current/low
voltage. In these low-power applications, multiple contacts can also be switched in series (e.g.,
“dry switching”). To preserve the gold plating on the contacts, do not exceed the following
max. values at any time:
High Current Rating: If higher loads must be switched through one or more of the contacts,
the minimum and maximum values of the contact(s) changes to:
Min. voltage: 15V ac/dc
Min. current: 30 mA ac/dc
Min. power: 0.45 W (0.45 VA)
Min. voltage: 1V ac/dc
Min. current: 5 mA ac/dc
Min. power: 5 mW (5 mVA)
Banner Engineering Corp. - Minneapolis, MN
Specifications
USA - Tel: 763.544.3164
Max. voltage: 250V ac/dc
Max. current:
Max. power:
Max. voltage: 60V
Max. current: 300 mA
Max. power: 7 W (7 VA)
UM-FA-9A: 6 A
UM-FA-11A: 7 A
UM-FA-9A: 200 W (1,500 VA)
UM-FA-11A: 200 W (1,750 VA)
15