CVM1-PA208 Omron, CVM1-PA208 Datasheet - Page 69

no-image

CVM1-PA208

Manufacturer Part Number
CVM1-PA208
Description
CV/CVM1 POWER SUPPLY, AC
Manufacturer
Omron
Datasheet

Specifications of CVM1-PA208

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
3-3-2 Control Panel
Installation
30 mm
min.
40 mm
min.
Input duct
30 mm min.
Fuses, relays, timers (Do not
install heat-generating
equipment or power equipment.)
Allow at least 40 mm of clear space at the top of every Rack and 30 mm at the
bottom of every Rack.
When mounting the PC in a control panel, mount the Racks to an intermediate
plate. Holes for mounting the Racks to the intermediate plate should be drilled at
intervals shown in the following diagram. Completely ground the intermediate
mounting plates. Use conductor-plated plates to improve noise immunity.
30 mm min.
Output duct
Terminal
blocks for PC
200 mm min.
Terminal blocks for
power equipment
Power duct
Section
3-3