XTPR032BC1 Eaton / Control Automation, XTPR032BC1 Datasheet - Page 2
XTPR032BC1
Manufacturer Part Number
XTPR032BC1
Description
MANUAL MOTOR PROTECTOR; ROTARY TYPE; FRAME B; CLASS 10; 25-32 AMP
Manufacturer
Eaton / Control Automation
Type
Motor Protectorr
Datasheet
1.XTPR010BC1.pdf
(7 pages)
Specifications of XTPR032BC1
Brand/series
XT Series
Current, Rating Max
32
Dimensions
45mmL×94mmW×93mmH
Horsepower, Max, 3 Phase, At 200 V
7.5
Horsepower, Max, 3 Phase, At 240 V
10
Horsepower, Max, 3 Phase, At 480 V
25
Horsepower, Max, 3 Phase, At 600 V
30
Ip Rating
IP20
Motor, Amp, Full Load
25-32
Mounting Type
DIN Rail
Power, Rating
15 kW
Primary Type
Motor Protector
Standards
UL, CSA, VDE
Switch Type
Rotary
Terminal Type
Screw
Termination
Screw
Lead Free Status / Rohs Status
RoHS Compliant part
For Use With
3-Phase Motor
52
Manual Motor Protectors
XTPR032BC1
XTPR063DC1
• Type 1 and Type 2 Coordination
• Motor Protective Device with Thermal and Magnetic Trip.
• Select Manual Motor Protectors by full load current. Maximum Motor Ratings (kW) are for reference
• Type 1 and Type 2 Coordination
• Motor Protective Device with Thermal and Magnetic Trip.
• Select Manual Motor Protectors by full load current. Maximum Motor Ratings (kW) are for reference
Rated
Uninterrupted
Current —
I
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
10
12
16
20
25
32
Rated
Uninterrupted
Current —
I
16
25
32
40
50
58
65
u
u
Manual Motor Protectors, Rotary, Frame B, Screw Terminals
only.
Manual Motor Protectors, Rotary, Frame D, Screw Terminals
only.
= I
= I
e
e
(Amps)
(Amps)
FLA
Adjustment
Range /
Overload
Release —
I
FLA
Adjustment
Range /
Overload
Release —
I
0.1 – 0.16
0.16 – 0.25
0.25 – 0.4
0.4 – 0.63
0.63 – 1
1 – 1.6
1.6 – 2.5
2.5 – 4
4 – 6.3
6.3 – 10
8 – 12
10 – 16
16 – 20
20 – 25
25 – 32
10 – 16
16 – 25
25 – 32
32 – 40
40 – 50
50 – 58
55 – 63
r
r
(Amps)
(Amps)
Short
Circuit
Release —
I
Short
Circuit
Release —
I
2.2
3.5
5.6
8.8
14
22
35
56
88
140
168
224
280
350
448
224
350
448
560
700
812
882
rm
rm
(Amps)
(Amps)
Maximum Motor Ratings
Maximum kW Rating
AC-3 — P (kW)
3-Phase
220 –
240V
Maximum Motor Ratings
Maximum kW Rating
AC-3 — P (kW)
3-Phase
220 –
240V
—
—
0.06
0.09
0.12
0.25
0.37
0.75
1.1
2.2
3
4
5.5
5.5
7.5
4
5.5
7.5
11
14
17
18.5
380 –
415V
380 –
415V
—
0.06
0.09
0.12
0.25
0.55
0.75
1.5
2.2
4
5.5
7.5
9
12.5
15
7.5
12.5
15
20
25
30
34
440V
440V
—
0.06
0.12
0.18
0.25
0.55
1.1
1.5
3
4
5.5
9
11
12.5
15
9
12.5
17.5
22
30
37
37
500V
500V
—
0.06
0.12
0.25
0.37
0.75
1.1
2.2
3
4
5.5
9
12.5
15
22
9
12.5
17.5
22
30
37
37
660 –
690V
660 –
690V
0.06
0.12
0.18
0.25
0.55
1.1
1.5
3
4
7.5
11
12.5
15
22
30
12.5
22
22
30
45
55
55
list number
list number
Eaton
Eaton
XTPRP16BC1
XTPRP25BC1
XTPRP40BC1
XTPRP63BC1
XTPR001BC1
XTPR1P6BC1
XTPR2P5BC1
XTPR004BC1
XTPR6P3BC1
XTPR010BC1
XTPR012BC1
XTPR016BC1
XTPR020BC1
XTPR025BC1
XTPR032BC1
XTPR016DC1
XTPR025DC1
XTPR032DC1
XTPR040DC1
XTPR050DC1
XTPR058DC1