Horizontal Link Identification – Cables
Section 5.1.2 States
A horizontal link identifier, unique within the building, shall be assigned to each horizontal link and to its elements.
Each end of a horizontal cable shall be labeled within 300mm (12 inches) of the end of the cable jacket with the
horizontal link identifier, which shall be visible on the exposed part of the cable jacket. This shall include each
cable in the Telecommunications Space (TS), at the work area, and at a Consolidation Point (CP), if present.
A horizontal link identifier shall have a format of “fs-an” where:
For example:
Section 6.1.1 States
A unique building backbone cable identifier shall be assigned to each backbone cable between two TS’s in one
building and it shall have a format of “fs
In this format, the TS with the lesser alphanumeric identifier shall be listed first. If the entire cable is within one
TS, the format may be fs
same format where possible. The backbone cable identifier shall be marked on each end of the backbone cable
within 300mm (12 inches) of the end of the cable jacket.
For example:
Panduit labels for laser/ink jet printers and hand-held thermal transfer printers can be
generated by a mechanical device and are made of durable polymer construction that will
withstand the effects of moisture, heat, and time.
f =
s =
a =
n =
“1A-B01” = cable origination point first
floor, TS A, patch panel B, position 01
fs
fs
n = one to two alphanumeric characters identifying a single cable with one end terminated in the TS
“1A/2A-1” = TS A on first floor to TS A
on second floor, cable 1
1
2
= TS identifier for the space containing the termination of one end of the backbone cable
= TS identifier for the space containing the termination of the other end of the backbone cable
designated fs
numeric character(s) identifying the floor of the building occupied by the TS
alpha character(s) uniquely identifying the TS on floor f, or the building area in which the space
is located
one to two alpha characters uniquely identifying a single patch panel or a group of patch panels with
sequentially numbered ports, an IDC connector or a group of IDC connectors serving as part of the
horizontal cross-connect
two to four numeric characters designating the port on a patch panel in the TS or the section of an
IDC Connector on which a four pair horizontal cable is terminated in the TS
1
1
/fs
and the other end terminated in the TS designated fs
1
-n. All building backbone cable identifiers in a single infrastructure should have the
1
/fs
2
-n” where: