DR-30-5 Mean Well, DR-30-5 Datasheet

Linear & Switching Power Supplies 15W 5V 3A

DR-30-5

Manufacturer Part Number
DR-30-5
Description
Linear & Switching Power Supplies 15W 5V 3A
Manufacturer
Mean Well
Datasheet

Specifications of DR-30-5

Product
Switching
Commercial/medical
Commercial
Output Power Rating
15 W
Input Voltage
85 VAC to 264 VAC, 120 VDC to 370 VDC
Number Of Outputs
1
Output Voltage (channel 1)
5 V
Output Current (channel 1)
3 A
Mounting Style
DIN Rail
Output Type
DC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
EMI CONDUCTION & RADIATION
INRUSH CURRENT (Typ.)
OVERLOAD
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
30W Single Output Industrial DIN Rail Power Supply
Note.3
Note.2
5V
3A
0 ~ 3A
15W
80mVp-p
4.75 ~ 5.5V
100ms, 30ms/230VAC
100ms/230VAC
85 ~ 264VAC
47 ~ 63Hz
DR-30-5
0.88A/115VAC
105 ~ 160% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +60
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL60950-1, TUV EN60950-1 a
I/P-O/P:3KVAC
I/P-O/P:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
441.5K hrs min.
78*93*56mm (W*H*D)
0.27Kg; 48pcs/14Kg/1.02CUFT
74%
COLD START 15A/115VAC
2.0%
1.0%
1.0%
0.03%/
(0 ~ 50
(Refer to output load derating curve)
120 ~ 370VDC
MIL-HDBK-217F (25 )
0.48A/230VAC
21ms/115VAC at full load
100ms, 30ms/115VAC at full load
pproved, Design refer to
12V
2A
0 ~ 2A
24W
120mVp-p
10.8 ~ 13.2V
DR-30-12
13.8 ~ 16.2V
81%
30A/230VAC
1.0%
1.0%
1.0%
EN50178
15V
2A
0 ~ 2A
30W
120mVp-p
13.5 ~ 16.5V
DR-30-15
17.25 ~ 20.25V
82%
1.0%
1.0%
1.0%
D R - 3 0
DR-30-24
24V
1.5A
0 ~ 1.5A
36W
150mVp-p
21.6 ~ 26.4V
27.6 ~ 32.4V
83%
File Name:DR-30-SPEC 2008-04-07
1.0%
1.0%
1.0%
s e r i e s

Related parts for DR-30-5

DR-30-5 Summary of contents

Page 1

... Single Output Industrial DIN Rail Power Supply SPECIFICATION MODEL DR-30-5 DC VOLTAGE 5V RATED CURRENT 3A CURRENT RANGE RATED POWER 15W RIPPLE & NOISE (max.) 80mVp-p Note.2 OUTPUT VOLTAGE ADJ. RANGE 4.75 ~ 5.5V VOLTAGE TOLERANCE Note.3 LINE REGULATION LOAD REGULATION SETUP, RISE TIME 100ms, 30ms/230VAC HOLD UP TIME (Typ ...

Page 2

... POWER & SWITCH- FILTER ING CONTROL O.L.P. Output Derating VS Input Voltage 100 (VERTICAL Case No. 918B Unit: 46.5 46 RECTIFIERS & FILTER DETECTION CIRCUIT O.V.P. 95 100 115 120 140 160 180 200 220 INPUT VOLTAGE (VAC) 60Hz File Name:DR-30-SPEC 2008-04- Ta=25 240 264 ...

Related keywords