0LD35553Z Littelfuse Inc, 0LD35553Z Datasheet

FUSE DIST BLOCK 350A 600V 3POLE

0LD35553Z

Manufacturer Part Number
0LD35553Z
Description
FUSE DIST BLOCK 350A 600V 3POLE
Manufacturer
Littelfuse Inc
Type
Power Distribution Blockr
Series
POWR-BLOKS® LDr
Datasheet

Specifications of 0LD35553Z

Number Of Poles
3
Current Rating
350A
Voltage - Rated
600V
Line Side Connections Per Pole
2
Load Side Connections Per Pole
6
Line Side Connection Type
Screw Connection
Load Side Connection Type
Screw Connection
Line Side Wire/stud Size
2/0 - #14CU/AL
Load Side Wire/stud Size
4 - #14CU/AL
Product
Block
Voltage Rating
600 Volts
Mounting Style
Panel
Body Material
Phenolic
Size (lxwxh)
127 mm x 102 mm x 66.2 mm
Termination Style
Crimp
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
LD35553Z
POWR-BLOKS
Distribution/Splicer Blocks and Covers
POWR-BLOKS power distribution blocks offer a safe, convenient way
of splicing cables, providing a fixed junction tap-off point or splitting
primary power into secondary circuits. LX2xxx-DIN series offers integral
DIN-Rail mount and an optional hinged safety cover.
Applications
Typical applications include heating, air conditioning and refrigeration
systems, elevator systems, material handling equipment, control
panels, motor controls, switchgear, and anywhere power needs to be
distributed to more than one load.
Specifications
Voltage Rating:
Amperage:
Material:
© 2005 Littelfuse
POWR-GARD
600V
Based on NEC Table 310.16,
using 75°C copper wire
Phenolic rated at 150°C and Thermoplastic rated at
125°C (LD1400 and LS1300 series only)
Products Catalog
w w w . l i t t e l f u s e . c o m
Blocks and Holders
Connectors
Box lug connectors are designed for use with a single, solid or class
B or C stranded conductor. Use of more than one conductor per
connector opening or use of extra-flexible, fine stranded conductors,
such as welding cable, voids the UL Listing, and may cause overheating.
Manufacturers of cable terminations can furnish crimp-on sleeves for
fine stranded conductors which permit these conductors to be used with
box lugs.
Ampere Ratings
The ampere rating per pole for power distribution blocks is based on
the line ampacity of 75°C insulated conductors per NEC Table 310.16. If
60°C insulated conductors are used, load must not exceed the ampacity
of 60°C conductors. Use of conductors rated in excess of 75°C is
permitted (for example 90°C), however, load must not exceed the
ampacity of 75°C conductors.
Ordering Information
Note: Aluminum blocks can use copper or aluminum wire; copper blocks can
only use copper wire.
Connector:
Flammability Rating:
Approvals:
Distribution Block
Example Part No.
Standard: Highly conductive aluminum, tin plated
Copper: Highly conductive copper, tin plated
94V-0
UL Recognized (File No. E171395)
CSA Certified (File No. LR700111)
Example Part No.
Splicer Block
137

Related parts for 0LD35553Z

0LD35553Z Summary of contents

Page 1

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers POWR-BLOKS power distribution blocks offer a safe, convenient way of splicing cables, providing a fixed junction tap-off point or splitting primary power into secondary circuits. LX2xxx-DIN series offers integral DIN-Rail mount and an optional ...

Page 2

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers Littelfuse optional power distribution block covers provide protection against accidental shorting between poles caused by loose wires, tools, or other conductive material. They also protect personnel from accidentally contacting energized connectors. Clear plastic covers ...

Page 3

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers Distribution Block Selection Guide Connector Configuration Mat’l Line Load © 2005 Littelfuse POWR-GARD Products Catalog ™ • ...

Page 4

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers Distribution Block Selection Guide Connector Configuration Mat’l Line Load 140 Blocks and Holders Line Amp Number Rating of Poles Openings Wire Range per Pole 760 1 500mcm-#4 ...

Page 5

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers Splicer Block Selection Guide Connector Configuration Mat’l Line Load © 2005 Littelfuse POWR-GARD Products Catalog ™ • Blocks and Holders Line ...

Page 6

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers LX0XXX .218 x .375" .07" [5.5 x 9.5]SLOT [1.8] 3.38" [85.8] 3.52" [89.3] 4.13" [104.8] 2 POLE LX1XXX 1.52 [38.7] 1 POLE LX2XXX 1.13" [28.6] .31" .56" [7.9] [14] 2.25" [57.2] 2.88" 2.88" [73.0] ...

Page 7

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers LX2XXX-XDIN 2.42 [61.5] 3 POLE 1.94" LX3XXX [49.3] .97" [25] 3.38" 3.38" (85.7) (85.7) 4.00" 4.00" [102] [102] 1.17" .31" .31" [7.9] [29.7] [7.9] 1 POLE © 2005 Littelfuse POWR-GARD Products Catalog ™ • ...

Page 8

POWR-BLOKS ™ Distribution/Splicer Blocks and Covers LX4XXX 2.28" .31" [57.9] .31" [7.9] 1.14" [7.9] ] [29.0 4.13" 4.13" [105] [105] 4.75" 4.75" [121] [121] 1 POLE LX5XXX 3.17" [80.4] 1.58" [40.2] 4.75" 4.75" [121] [121] 5.50" 5.50" [140] [140] .37" ...

Related keywords