G2PF400VS02 TELE, G2PF400VS02 Datasheet

RELAY, VOLTAGE MONTR, 3-PHASE, 2 CO

G2PF400VS02

Manufacturer Part Number
G2PF400VS02
Description
RELAY, VOLTAGE MONTR, 3-PHASE, 2 CO
Manufacturer
TELE
Series
GAMMAr
Datasheet

Specifications of G2PF400VS02

Contact Configuration
DPCO
Power Consumption
9VA
Supply Voltage Max
400V
Relay Mounting
DIN Rail
Control Voltage Type
AC
Svhc
No SVHC (18-Jun-2010)
Contact Current Ac Max
5A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Monitoring relays - GAMMA series
Monitoring of phase sequence and phase failure
Detection of reverse voltage
Connection of neutral wire optional
Supply voltage = measuring voltage
2 change-over contacts
Width 22.5mm
Industrial design
Technical data
1. Functions
Monitoring of phase sequence, phase failure and detection of return
voltage (by means of evaluating the asymmetry)
2. Time ranges
Start-up suppression time:
Tripping delay:
3. Indicators
Green LED ON:
Yellow LED ON/OFF:
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
5. Input circuit
Supply voltage:
Tolerance:
Rated frequency:
Rated consumption:
Duration of operation:
Reset time:
Residual ripple for DC:
Drop-out voltage:
Overvoltage category:
Rated surge voltage:
6. Output circuit
2 potential free change-over contacts
Rated voltage:
Switching capacity (distance <5mm): 750VA (3A / 250V AC)
Switching capacity (distance >5mm): 1250VA (5A / 250V AC)
Fusing:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
3(N)~ 115/66V
3(N)~ 230/132V
3(N)~ 400/230V
3(N)~ 115/66V
3(N)~ 230/132V
3(N)~ 400/230V
3(N)~ 115/66V
3(N)~ 230/132V
3(N)~ 400/230V
Voltage monitoring in 3-phase mains
Adjustment range
fixed, max. 500ms
fixed, max. 350ms
indication of supply voltage
indication of relay output
terminals (N)-L1-L2-L3 (G2PF115VS02)
(= measuring voltage)
terminals (N)-L1-L2-L3 (G2PF230VS02)
(= measuring voltage)
terminals (N)-L1-L2-L3 (G2PF400VS02)
(= measuring voltage)
3(N)~ 99 to 132V (G2PF115VS02)
3(N)~ 198 to 264V (G2PF230VS02)
3(N)~ 342 to 457V (G2PF400VS02)
48 to 63Hz
3VA (G2PF115VS02)
6VA (G2PF230VS02)
9VA (G2PF400VS02)
100%
<100ms
-
>20% of the supply voltage
III (in accordance with IEC 60664-1)
4kV
250V AC
5A fast acting
www.tele-online.com
Mechanical life:
Electrical life:
Switching frequency:
Overvoltage category:
Rated surge voltage:
7. Measuring circuit
Measured variable:
Input:
Overload capacity:
Input resistance:
Asymmetry:
Overvoltage category:
Rated surge voltage:
8. Accuracy
Base accuracy:
Frequency response:
Adjustment accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence: ≤0.05% / °C
9. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature: -25 to +70°C
Relative humidity:
Pollution degree:
Vibration resistance:
Shock resistance:
3(N)~ 115/66V
3(N)~ 230/132V
3(N)~ 400/230V
3(N)~ 115/66V
3(N)~ 230/132V
3(N)~ 400/230V
3(N)~ 115/66V
3(N)~ 230/132V
3(N)~ 400/230V
20 x 10
2 x 10
at 1000VA resistive load
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
III (in accordance with IEC 60664-1)
4kV
AC Sinus, 48 to 63Hz
terminals (N)-L1-L2-L3 (G2PF115VS02)
(= supply voltage)
terminals (N)-L1-L2-L3 (G2PF230VS02)
(= supply voltage)
terminals (N)-L1-L2-L3 (G2PF400VS02)
(= supply voltage)
3(N)~ 132/76V (G2PF115VS02)
3(N)~ 264/152V (G2PF230VS02)
3(N)~ 457/264V (G2PF400VS02)
5kΩ (G2PF115VS02)
10kΩ (G2PF230VS02)
15kΩ (G2PF400VS02)
fixed, typ. 30%
III (according to IEC 60664-1)
4kV
≤3% (of maximum scale value)
-
-
≤2%
-
-25 to +55°C (in accordance with IEC 60068-1)
-25 to +40°C (in accordance with UL 508)
-25 to +70°C
15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
3 (in accordance with IEC 60664-1)
10 to 55Hz 0.35mm
(in accordance with IEC 60068-2-6)
15g 11ms (in accordance with IEC 60068-2-27)
5
6
operations
operations
G2PF...S02

Related parts for G2PF400VS02

G2PF400VS02 Summary of contents

Page 1

... Tolerance: 3(N)~ 115/66V 3(N 132V (G2PF115VS02) 3(N)~ 230/132V 3(N)~ 198 to 264V (G2PF230VS02) 3(N)~ 400/230V 3(N)~ 342 to 457V (G2PF400VS02) Rated frequency 63Hz Rated consumption: 3(N)~ 115/66V 3VA (G2PF115VS02) 3(N)~ 230/132V 6VA (G2PF230VS02) 3(N)~ 400/230V 9VA (G2PF400VS02) ...

Page 2

... Phase failure monitoring When one of the three phases fails, the output relays switch into off-position (yellow LED not illuminated). RELEASE 2009/07 Subject to alterations and errors Connections Dimensions www.tele-online.com G2PF...S02 ...

Related keywords