MY2K 24DC Omron, MY2K 24DC Datasheet - Page 2

POWER RELAY, DPDT, 24VDC, 10A, PLUG IN

MY2K 24DC

Manufacturer Part Number
MY2K 24DC
Description
POWER RELAY, DPDT, 24VDC, 10A, PLUG IN
Manufacturer
Omron
Datasheet

Specifications of MY2K 24DC

Relay Type
General Purpose
Coil Voltage Vdc Nom
24V
Contact Current Max
10A
Contact Voltage Ac Nom
250V
Contact Voltage Dc Nom
30V
Coil Resistance
636ohm
Contact Configuration
DPDT
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications
■ Coil Ratings
Note: 1. For AC models, the rated current values are half-wave rectified current values measured with a DC ammeter.
■ Contact Ratings
*Note:
■ Characteristics
Note: The data shown above are initial values.
2
AC
DC
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching power
Failure rate* (reference value)
Contact resistance
Set time
Reset time
Max. operating frequency
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Endurance
Ambient temperature
Ambient humidity
Weight
Rated voltage
2. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for AC rated current and
3. The AC coil resistance values are for reference only.
4. Performance characteristic data are measured at a coil temperature of 5°C to 35°C.
12 V
24 V
50 V
100 V
12 V
24 V
±15% for DC rated current, and +15% for DC coil resistance.
P level: λ
General-purpose Latching Relay
57 mA
27.5 mA 26.4 mA 320 Ω
14.0 mA 13.4 mA 1,400 Ω
7.1 mA
110 mA
52 mA
Item
60
50 Hz
Rated current
= 0.1 x 10
56 mA
6.9 mA
60 Hz
-6
Set coil
/operation
72 Ω
5,400 Ω
110 Ω
470 Ω
Resistance
50 mΩ max.
Time:
Min. pulse width:
Time:
Min. pulse width:
Mechanical: 18,000 operations/hr
Electrical:
100 MΩ min. (at 500 VDC)
1,500 VAC, 50/60 Hz for 1 min (1,000 VAC between contacts of same polarity and between set and reset
coils)
Destruction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Destruction: 1,000 m/s
Malfunction: 200 m/s
Mechanical: 100,000,000 operations min. (at 18,000 operations/hr)
Electrical:
Operating:
Operating: 5% to 85%
Approx. 30 g
3 A at 220 VAC, 3 A at 24 VDC
3 A
250 VAC, 125 VDC
3 A
660 VA, 72 W
1 mA at 1 VDC
39 mA
18.6 mA 18.1 mA 550 Ω
3.5 mA
3.5 mA
50 mA
25 mA
1,800 operations/hr (under rated load)
200,000 operations min. (at 1,800 operations/hr)
–55°C to 60°C (with no icing)
Resistive load (cosφ = 1)
50 Hz
MYK
Rated current
2
38.2 mA 130 Ω
3.4 mA
3.4 mA
2
60 Hz
Reset coil
AC: 30 ms max.; DC: 15 ms max.
AC: 60 ms.; DC: 15 ms.
AC: 30 ms max.; DC: 15 ms max.
AC: 60 ms.; DC: 15 ms.
3,000 Ω
3,000 Ω
235 Ω
940 Ω
Resistance
80%
max.
Must-set
voltage
0.8 A at 220 VAC, 1.5 A at 24 VDC
176 VA, 36 W
% of rated voltage
Inductive load (cosφ = 0.4) (L/R = 7 ms)
80%
max.
voltage
Must-
reset
110%
voltage
Max.
0.6 to 0.9
(60 Hz)
1.3 W
Set coil
consumption
(Approx.)
Power
0.2 to 0.5
(60 Hz)
0.6 W
Reset
coil

Related parts for MY2K 24DC