2469-32-33-2-AHD-1 YOKOGAWA, 2469-32-33-2-AHD-1 Datasheet - Page 3

TRANSDUCER, TRUE RMS VOLTAGE, 20mA

2469-32-33-2-AHD-1

Manufacturer Part Number
2469-32-33-2-AHD-1
Description
TRANSDUCER, TRUE RMS VOLTAGE, 20mA
Manufacturer
YOKOGAWA
Datasheet

Specifications of 2469-32-33-2-AHD-1

Transducer Function
True RMS Voltage
Accuracy %
0.5%
Output Current Max
20mA
Operating Temperature Range
-20°C To +60°C
External Depth
95.72mm
Frequency Max
60Hz
Frequency Min
50Hz
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
1) GENERAL
2) SPECIFICATIONS
3) STANDARD MODELS
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Model #
Input Current
Input over range capability
Input Burden
Rated outputs
Accuracy 10-100% of rated input
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Input frequency range
Influence of frequency
Weight
Shock
Vibration
UL Recognition
TRMS / 0-1mA output / 120V aux. power
AVG./4-20mA output / 120V aux. power
The 2469 and 2489 AC Average Current transducers produce an analog DC signal output corresponding to
the average value of the AC input. The true RMS versions always require external power and produce an
analog DC output corresponding to the true RMS value of the input signal.
3 in 1 / 0-1mA output / self-powered
AVG./0-1 mA output / self powered
TRMS / 4-20mA / 120V aux. power
Auxiliary power supply options <5.0 VA burden.
0-5 Amp AC, 60 HZ input
J U X T A
A C
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
C U R R E N T
Zero: ±1% minimum(AHD only) Zero: ±5% minimum(AHD only)
IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV, 1.2 x 50 microseconds)
< 0.2%, 45-65 Hz, fundamental through 9th harmonic (TRMS models only)
0-1mADC=±0.5% of full scale
4-20mADC=±0.5% of span
4-20 mADC into 750Ω max. load; 15VDC output compliance
0-1mADC into 10 kΩ max. load; 10VDC output compliance
2000 VAC aux. power to output and case (AHD and TRMS)
± 250 PPM / °C of span
Span: ± 2% minimum
2469 (0.5% Accuracy)
TRMS = 900g, 0-1mA = 358g, 4-20mA = 897g, 3 in 1 = 1100g
246921-380-AFA-0
246931-380-AFA-1
246921-380-AHD-1
246931-380-AHD-1
246923-380-AFA-0
>10 megohm / 500VDC input/output/power/case
2
0 - 90% relative humidity (non-condensing)
2500 VAC input to output, power and case
< 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
2469
< 0.2% after 50G, 3 Axis and 6 repetitions
T R A N S D U C E R S
<400 milliseconds(0-99% of output)
50 - 500 Hz < 0.2% effect on accuracy
1000% of rated input for 5 seconds
200% of rated input continuous
0-1 Amp AC or 0-5 Amp AC
500 VAC output to case
<0.2VA per element
< 0.2% at 400 AT/m
-20°C to +60°C
File # E60579
0-1mADC=±0.2% of full scale
4-20mADC=±0.2% of span
Span: ± 10% minimum
± 140 PPM / °C of span
2489 (0.2% Accuracy)
248921-380-AFA-0
248931-380-AFA-1
248921-380-AHD-1
248931-380-AHD-1
248923-380-AFA-0
2489

Related parts for 2469-32-33-2-AHD-1