LIGHT ECO 3.8 FAIRFORD ELECTRONICS, LIGHT ECO 3.8 Datasheet - Page 6

no-image

LIGHT ECO 3.8

Manufacturer Part Number
LIGHT ECO 3.8
Description
CONTROLLER, LIGHT, ECO 3.8
Manufacturer
FAIRFORD ELECTRONICS
Datasheet

Specifications of LIGHT ECO 3.8

Power Rating
1.9kW
Approval Bodies
CE, EN 55015, 60598, 60742, 61000, AS/NZS 3350.1, C-Tick
External Depth
100mm
External Length / Height
305mm
External Width
170mm
For Use With
Fluorescent Lighting
Lead Free Status / RoHS Status
na
Operation
Light Eco Plus is fully automatic and requires no user operation to perform its intended task of
saving more than 25% of the lighting power on the circuit.
Principle of operation
Discharge lighting such as fluorescent lighting requires high power to start up but once
operating at full temperature and output, can operate at reduced power with minimal impact on
performance while saving more than 25% of power.
Light Eco Plus is a microprocessor controlled device which allows the lights to power up
correctly and, when conditions are appropriate, switches to economy mode and automatically
reduces the power to the lights.
While in economy mode Light Eco Plus constantly monitors the power and returns to full
power mode if required. Typically this will be due to another bank of lights being turned on or a
critical drop in supply power. It may also be because off an operator intervention to perform
lamp maintenance.
User Display
Light Eco Plus has a display on the front panel which gives immediate indication of its operation
and energy saving.
Bypass switch activated
Supply voltage too low
Lights switched on
New lighting load
After bypass or
programming
Condition
Economy
Lights off
Overload
Warm Up
240 V, 11 A, 2.1kW
Eco Saves
240 V, 7.9 A, 1.5kW,
Low Mains Voltage
216 V, 10 A, 1.9kW
Overload (flashing)
245 V, 21 A, 4.1kW
Lights Off
Bypass Mode
43 minutes
Display
28%
Power (in Kilowatts) and percentage power
warming up. Unit in full power mode. Volts,
power mode. Unit will return to Economy
Lights have just been turned on and are
Unit has been commanded into Bypass
Mode for lamp maintenance. Unit in full
Unit has detected critical drop in Mains
Voltage. Unit in full power mode. Volts,
Unit is in economy mode. Volts, Amps,
Unit in full power safe mode. Circuit
Lights are off and unit is in standby
Amps and Power (in Kilowatts) is
Amps and Power (in Kilowatts) is
breaker on lights is likely to trip
mode in 43 minutes
saving is displayed
Description
displayed
displayed

Related parts for LIGHT ECO 3.8