8536SDG1V02S SQUARE D, 8536SDG1V02S Datasheet - Page 17

Magnetic Motor Starter

8536SDG1V02S

Manufacturer Part Number
8536SDG1V02S
Description
Magnetic Motor Starter
Manufacturer
SQUARE D
Datasheet

Specifications of 8536SDG1V02S

No. Of Phases
Three
Power Rating
25hp
Current Rating
45A
Peak Reflow Compatible (260 C)
No
Supply Voltage Max
460VAC
Control Voltage Max
120V
Leaded Process Compatible
No
Switch Function
3PST
Supply Voltage Range
110VAC To 120VAC
Rohs Compliant
No
Contact Rating
45A
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Application Data – Class 8502, 8536
16
Size 6 Starter 8536 SH
Size 7 Starter 8536 SJ
Size 6 Type SH and Size 7 Type SJ Contactors
and Starters
Size 6 Type SH and Size 7 Type SJ contactors and
starters have a DC coil operated by a solid state
rectifier circuit mounted on the device and
powered from an ac source. The Size 6 and 7 are
equipped as standard with a fused control circuit
transformer (Form F4T) rated 240/480-120 volts
60 hertz, 220/440-110 volts 50 hertz. The purpose
of this transformer is to provide an isolated 120
volts 60 hertz, 110 volts 50 hertz, supply for the
control circuit. Size 6 and 7 devices may be
ordered for other system voltages by specifying
the voltage and frequency desired.
Operation Rates
Continuous operation rate: 3 operations/minute
maximum. Jogging or Plugging Duty: 15
operations/minute – 3 minutes maximum.
Field conversion for other system voltages is
accomplished by one of the following methods,
NOT BY THE USUAL PRACTICE OF CHANGING
THE COIL:
1. If the factory wiring is indicated as being for
2. If the factory wiring is indicated as being for
3. The standard transformer supplied may be
480 volts 60 hertz, 440 volts 50 hertz,
conversion to 240 volts 60 hertz, 220 volts 50
hertz, can be accomplished by reconnecting
the control transformer as illustrated on
instruction sheet supplied with the controller.
This is the same method that would be used
on Class 9070 control circuit transformers.
Conversion to any other voltage requires
replacement of the control transformer. For
other system voltages: i.e. 208, 277, 380, 600
volts, a new transformer with single voltage
primary must be selected from table at right.
Control transformer connections are
illustrated on the instruction sheet supplied
with the controller.
any voltage other than 480 volts 60 hertz, 440
volts 50 hertz, conversion to any other voltage
requires replacement of the control
transformer. Refer to table at right.
used to power a maximum of five Class 9001
Type K illuminated operators powered with
transformer type light modules. When extra
capacity to power control relays or other
inductive loads is required, a second
transformer must be added. Extra capacity
can be purchased as Form F4T with additions
in 100 VA increments.
© 1998 Square D All Rights Reserved
4. Standard controllers are wired for common
The tables below give the replacement
transformers for Type S Sizes 6 and 7 contactors
and starters. To change voltages on these
devices, coils are not changed, instead
transformers with the desired voltage are
changed.
Replacement Control Transformers for Type S
Size 6
Replacement Control Transformers for Type S
Size 7
Auxiliary Contacts
A N.O. holding circuit contact and a N.C. auxiliary
contact are provided as standard. The holding
circuit contact may or may not be required for
either 3-wire or 2-wire control. Size 6 and 7
devices have an additional N.C. auxiliary contact
which is wired in the coil control circuit. DO NOT
USE THIS N.C. CONTACT FOR ANY OTHER
PURPOSE.
Voltage
60 Hertz
240/480-120
208-120
277-120
. . .
600-120
120-120
240-120
Voltage
60 Hertz
240/480-120
208-120
277-120
. . .
600-120
120-120
240-120
control and are not convertible for operation of
the control circuit from a separate source of
supply voltage. Controllers designated Form S
have special wiring designed for separate
control. They are furnished with an isolating
transformer, usually having a 120 volt primary
and 120 volt secondary, that must not be
bypassed. Form S controllers are not
convertible for operation on common control.
50 Hertz
220/440-110
. . .
. . .
380-110
550-110
110-110
220-110
50 Hertz
220/440-110
. . .
. . .
380-110
550-110
110-110
220-110
Class 9070 Type
EO3S2A
EO3S2B
EO3S2C
EO3S2D
EO3S2E
EO3S2F
EO3S2G
Class 9070 Type
EO19S2A
EO19S2B
EO19S2C
EO19S2D
EO19S2E
EO19S2F
EO19S2G
5/98