E53-CNH01N2 Omron, E53-CNH01N2 Datasheet - Page 7

no-image

E53-CNH01N2

Manufacturer Part Number
E53-CNH01N2
Description
CARD OPTION RS232C+HB ALARM
Manufacturer
Omron
Datasheet

Specifications of E53-CNH01N2

Accessory Type
Heater Burnout/SSR Failure/Heater Overcurrent/RS-232C
Svhc
No SVHC (15-Dec-2010)
Signal Input Type
Event
For Use With
E5CN-H Controller
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Characteristics
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and
✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10°C max.
✽4. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.
Indication accuracy
Transfer output accuracy ±0.3% FS max.
Influence of temperature
✽2
Influence of voltage ✽2
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Affect of signal source
resistance
Insulation resistance
Dielectric strength
Vibration
resistance
Shock
resistance
Weight
Degree of protection
Memory protection
Setup Tool
Setup Tool port
Standards
EMC
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
Malfunction 10 to 55 Hz, 20 m/s
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s
Destruction 300 m/s
Approved
standards
Conformed
standards
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Thermocouple input (R, S, B, W, PLII): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
60 ms
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1 °C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0.0 to 3240.0 s (in units of 0.1 s)
0.0 to 3240.0 s (in units of 0.1 s)
0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
−19999 to 32400 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g
Front panel: IP66, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
CX-Thermo version 4.0 or higher
Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. ✽4
UL 61010-1, CSA C22.2 No. 1010-1
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Power Frequency Magnetic Field Immunity:
Voltage Dip/Interrupting Immunity:
2
2
, 3 times each in X, Y, and Z directions
, 3 times each in X, Y, and Z directions
2
for 10 min each in X, Y, and Z directions
Advanced Digital Temperature Controller
EN 61000-4-8
EN 61000-4-11
EN 61326
EN 55011 Group 1, class A
EN 61326
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
E5CN-H
7