63-13-215-6 SOLA HEVI DUTY, 63-13-215-6 Datasheet - Page 5

Voltage Regulator/Power Conditioner

63-13-215-6

Manufacturer Part Number
63-13-215-6
Description
Voltage Regulator/Power Conditioner
Manufacturer
SOLA HEVI DUTY
Series
MCRr
Datasheet

Specifications of 63-13-215-6

Suppressor Type
Power Line Conditioner
No. Of Outlets
6
Input Voltage
120VAC
Output Voltage
120V
Width
279.4mm
Height
279.4mm
Output Type
Fixed
External Height
11.00"
Output Power
1500 VA
Input Voltage (nominal)
120 V
Features
Harmonic Filtering
Mounting Type
Surface Mount
Number Of Outlets
4
Voltage Regulation
+/- 3 %
Voltage Regulation Accuracy
+/- 3 %
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Operating Characteristics of the CVS & MCR Series
Efficiency
The copper magnet wire and lamination material used in
Sola/Hevi-Duty ferroresonant products are selected to
achieve ef fi cien cies of 90% or higher. Whether or not an
external load is being served, current will be drawn from the
line whenever the primary is energized, since the capacitor
remains connected in the circuit.
Overload and Short Circuits
When the load is increased beyond the regulator’s rated
value, a point is reached where the output voltage sud den ly
col laps es and will not regain its normal value until the load is
partially released. Under direct short circuit, the load current
is limited to approximately 150-200% of the rated full load
value and the input watts to less than 10% of normal.
A constant voltage regulator will protect both itself and its
load against damage from ex ces sive fault currents. Fusing
of load currents may not be necessary. The actual value of
short-circuit current varies with the specifi c design and
rating. Units may be operated in defi nite ly at short-circuit.
This characteristic protects the unit itself as well as the load
and load circuit being served. Typical overload
per for mance is shown in Figure D.
36
1
Figure C: Power Factor
Power Protection and Conditioning
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solaheviduty.com.
Motor Loads
Because of the fast response time of the Sola circuit, any
current-limiting characteristic must be taken into account
for transient overloads such as motor starting and solenoid
operation. In general, the Sola constant voltage regulator
must have a ca pac i ty nearly equal to the max i mum de mand
made on it, even for an instant. To determine the power
rating of the regulator, peak motor-starting current or
so le noid inrush current should be measured or power factor
cor rect ing capacitors should be used to reduce the starting
VA of the load.
Response Time
An important advantage of Sola’s ferroresonant trans form er
is its fast response time compared with other types of AC
regulators. Transient changes in supply voltage are usually
corrected within 1-1/2 cycles or less; the output voltage
will not fl uctuate more than a few percent, even during this
interval.
Figure D: Overload Performance