TIS 600-124 TRACOPOWER, TIS 600-124 Datasheet - Page 3

PSU, DIN RAIL, 600W, 24V

TIS 600-124

Manufacturer Part Number
TIS 600-124
Description
PSU, DIN RAIL, 600W, 24V
Manufacturer
TRACOPOWER
Datasheet

Specifications of TIS 600-124

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
63Hz
Output Voltage
24V
Output Current
24A
Power Rating
600W
Input Voltage
93VAC To 132VAC /
No. Of Outputs
1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
All specifications valid at nominal input voltage, full load and +25 °C after warm-up time unless otherwise stated.
http://www.tracopower.com
Instruction manual can be downloaded under:
www.tracopower.com/productsts/tis_manual.pdf
General Specifications
Temperature ranges
Humidity (non condensing)
Pollution degree
Temperature coefficient
Switching frequency
Efficiency
Isolation
Reliability, calculated MTBF
(MIL-HDBK-217 E)
Safety standards
Safety approvals
Electromagnetic compatibility (EMC), Emissions
Electromagnetic compatibility (EMC), Immunity
Safety class
Case protection
Environment
Enclosure material
Mounting (snap-on with self locking spring)
Connection
– Operating (ambient temp.)
– Derating above 50 °C (122 °F)
– Storage (non operating)
– CB report
– UL approvals
– Conducted RI suppression on input
– Radiated RI suppression
– Harmonic current emissions
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity
– Immunity to conducted RF disturbances
– Power frequency field immunity
– Vibration
– Shock
TIS 50 ... TIS 300: 85 % typ.
TIS 500/600: 340’000 h @ +25 °C/300’000 h @ +25 °C
TIS 150/300: 420’000 h @ +25 °C/360’000 h @ +25 °C
TIS 50/75: 450’000 h @ +25 °C/420’000 h @ +25 °C
TIS 500: 90 % typ.
TIS 600: 90 % typ.
Industrial Power Supplies
TIS Series
– 25 °C to +70 °C
2 %/K
– 25 °C to +85 °C
95 % rel. H max.
2
0.02 %/K
80 kHz typ. (pulse width modulation)
according to IEC/ EN 60950, UL 60950, UL 508
IEC/ EN 60950-1 (SELV, except 72 VDC models)
UL/cUL 60950-1, UL 508, UL/cUL 1604
for IEC 60950
www.tracopower.com/products/tis_cb.pdf
UL/cUL 60950, File E181381
UL/cUL 508, File E210002
UL/cUL 1604, File E213613 not for TIS 50 & 500
(Class I, Div. 2, Groups A, B, C and D hazardous locations)
www.ul.com -> certifications
EN 61000-6-3 / EN 61000-6-4
EN 55011 class B, EN 55022 class B,
FCC part 15, level B
EN 55011 class A, EN 55022 class A,
FCC part 15, level A
EN 61000-3-2, class A
EN 61000-6-2
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
degree of electrical protection 1 (IEC 536)
IP 20 (IEC 529)
IEC 60068-2-6; 1 gn, 200 sweeps, each axis
IEC 60068-2-27; 15 gn, 11 ms, each axis
aluminium (chassis) / zinc plated steel (cover)
for 35 mm DIN-rails as per EN 50022
detachable screw terminal block
(plugs included)
(TIS 600: fixed screw terminal block)
(– 13 °F to +185 °F)
4 kV/8 kV
10 V/m
2 kV
2 kV/4 kV
10 V
30 A/m
(– 13 °F to +185 °F)
50–600 Watt
Page 3 of 3