SDU-850-5 SOLA HEVI DUTY, SDU-850-5 Datasheet - Page 2

UPS, 230V, 510W

SDU-850-5

Manufacturer Part Number
SDU-850-5
Description
UPS, 230V, 510W
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of SDU-850-5

Capacity (va / W)
850VA / 510W
Output Voltage
230V
Backup Time - Full Load
2min
Length
116mm
Width
281mm
Height
124mm
Weight
11.9lb
Output Type
Fixed
Supply Voltage Vac
230VAC
Mounting Type
DIN Rail
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
SDU DIN Rail UPS Specifications
* At full load.
36
Capacity (VA/Watts)
Load Power Factor
H x W x D in (mm)
Weight lbs (kg)
Voltage
Frequency
Voltage (Battery Mode)
Frequency
(On Battery)
Overload Protection
Short Circuit
Battery Type
Transfer Time
Back-up Time*
(minutes)
Recharge Time
Operating Temperature
Storage Temperature
Relative Humidity
Ambient Operation
Audible Noise
Safety
Elevation
Shock & Vibration
Mounting
Catalog Number
Uninterruptible Power Systems
To be mounted on DIN TS35/7.5 or TS35/15 rail system. Chassis mounting permissible via
applications in accordance with UL508 without
degree 3. FCC Part 15, Subpart B, Class A
derating. Overvoltage category 3, pollution
UL 1778 C-UL Recognized for industrial
optional brackets. Unit handles normal shock and vibration of industrial use and
UPS automatic shutdown if overload exceeds 105% of nominal at 20 seconds,
10.7 (4.7)
SDU500
contact Technical Services at (800) 377-4384 with any questions.
500/300
According to the International Safe Transit Association standard ISTA 2A.
4
120V (+10%, - 20%)
1-95% humidity non-condensing, 0-50°C up to 5,000 ft (1500m)
Sealed, Non-spillable, maintenance-free lead acid batteries
Visit our website at www.solaheviduty.com or
Output AC Parameters
Battery Parameters
Input Parameters
50 +/- 5 Hz or 60 Hz +/- 6 Hz (auto sensing)
Environmental
8 hours to 90% capacity after full discharge
Dimensions
120% at 10 seconds, 130% at 3 seconds
Standards
transportation without coming off rail.
4.88 x 11.1 x 4.55 (124 x 281 x 116)
< 40dBA (1 meter from surface)
UPS output cut off immediately
5°F to 140°F (-15°C to 60°C)
1% to 95%, non-condensing
11.4 (5.0)
32°F to 122°F (0°C to 50°C)
SDU850
850/510
5000 ft without derating
2
4 - 6 ms typical
Step sinewave
50 or 60 Hz
+/- 0.3 Hz
+/- 5%
0.6
EN61000-3-3, IEC801-2, IEC801-3,
EMC: EN50091-2, EN61000-3-2,
CE Marked; LVD: EN62040-1-1;
SDU500-5
11.5 (5.2)
500/300
IEC801-4, IEC1000-2-2.
4
230V (+/- 20%)
SDU850-5
11.9 (5.4)
850/510
2