LEDESLWH ETERNA, LEDESLWH Datasheet - Page 2

no-image

LEDESLWH

Manufacturer Part Number
LEDESLWH
Description
EMERGENCY EXIT SIGN, LED, WHITE
Manufacturer
ETERNA
Datasheet

Specifications of LEDESLWH

Length
545mm
Depth
370mm
Ip/nema Rating
IP20
Svhc
No SVHC (15-Dec-2010)
Approval Bodies
BS EN 60598-2-22
Battery Life (working)
3 Hours
Battery Voltage
3.6V
Colour
White
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Safety markings:
Read this first:
>
>
>
>
>
>
>
>
>
>
>
>
>
This light fitting must be installed in
accordance with the Building Regulations
making reference to the Wiring Regulations
BS7671. The Building Regulations may be
obtained from HMSO or viewed and
downloaded from www.communities.gov.uk
following the link for Building Regulations.
Switch off the mains before commencing
installation and remove the appropriate circuit
fuse.
Your emergency fittings should have their own
separate mains supply circuit and should not
share their supply with other lighting or
electrical devices.
Suitable for indoor use only.
Disconnect the product from the electrical
supply before flash or high voltage testing.
This product is suitable for installation on
flammable surfaces ( indicated by the "F" in a
triangle )
Before making fixing hole(s), check that there
are no obstructions hidden beneath the
mounting surface such as pipes or cables.
The chosen location of your new fitting should
allow for the product to be securely mounted
( e.g. to a ceiling joist ) and safely connected to
the mains supply ( lighting circuit ).
Ensure that the fitting will be accessible after
installation for maintenance.
If the location of your new fitting requires the
provision of a new electrical supply, the supply
must conform with the requirements of the
Building Regulations making reference to the
Wiring Regulations ( see above ).
Make connections to the electrical supply in
accordance with the following code:
This product must be connected to Earth.
The ballast/ PCB inside this luminaire is only
for use in this luminaire and should not be
Live - Brown or Red
Neutral - Blue or Black
Earth - Green and Yellow
>
Installation:
1) Undo the screws at each end of the ceiling box
2) Remove the mains wires from the terminal
3) Use the rear of the case as a template, mark
4) Thread your mains supply cable through the
5) Secure the rear of the case to your mounting
6) Secure the mains supply cables into the
7) Re-connect the wires from the fitting according
8) Replace the ceiling box cover and secure
9) Remove the battery cover and connect the
10) Restore the power supply.
11) The LED indicators should light to indicate
used in any other way.
You are advised at every stage of your
installation to double-check any electrical
connections you have made. After you have
completed your installation there are electrical
tests that should be carried out: these tests are
specified in the Wiring Regulations ( BS7671 )
referred to in the Building Regulations. If in
doubt, consult a qualified electrician.
and lift off the top cover.
block noting the position of each wire.
the position of the fixing holes on your
mounting surface.
large hole in the rear of the case.
surface using suitable fixings ( not supplied ).
terminal block according to the colour code
opposite
identification marked next to the terminal block
in the fitting.
to the colour code opposite and following the
terminal identification markings in the fitting.
Ensure that the wiring from the mains supply
corresponds to the wires from the fitting.
using the two screws removed earlier.
battery pack. See fig. 1&2 opposite. Close the
battery cover.
correct charging and the sign panel will also
light. The LEDs indicate the following function:
P= mains power O.K., C= batteries charging
O.K., T= fault.
and
following
the
terminal
Please keep this instruction booklet and test record in a
safe place. A fire officer or other authorised person may
To change the sign:
1) Undo the screw and remove the cover at the mains
2) Gently pull the sign out of the body—take care not to
3) Insert the new panel into the end of the body locating
4) Holding the panel at a slight angle, push the first steel
5) When the sign is almost in place, locate the second pin
6) Replace the cap and screw.
Operation checks:
Periodic testing should be carried out simulating failure of
supply, causing the fitting to be energised from it’s battery.
Interruption of supply should be carried out by pressing the
test button on the end of the fitting or by operation of a
local keyswitch or other isolation device. During this period
all fittings should be examined visually to ensure that they
function correctly. At the end of the test period the supply
shall be restored and all indicator lamps checked to ensure
that the normal supply has been restored. The duration of
the simulated failure shall be:-
>
>
>
want to see your record of inspection and testing.
cable end of the fitting.
lose the small steel pins fitted to the top of the panel.
the first steel pin in the track in the bottom of the body.
pin along the track towards the end of the fitting.
in the track and press the sign into the fitting until it is
central in the body.
Each month:
Isolate the power supply and check the sign is
illuminated. This test should last for no more than 45
minutes. Endorse the test record form supplied.
Every six months:
Isolate the power supply and check that the sign is still
illuminated after 1 hour. Endorse the test record form.
Once each year:
Isolate the power supply and check that the sign is still
illuminated after 3 hours. Endorse the test record form.
Fig.1—Battery cover
Battery / LED
connector
Fig.3
Fig.2
Fig.4