NSYCCOTHC SCHNEIDER, NSYCCOTHC Datasheet

THERMOSTAT, NC, ADJUSTABLE

NSYCCOTHC

Manufacturer Part Number
NSYCCOTHC
Description
THERMOSTAT, NC, ADJUSTABLE
Manufacturer
SCHNEIDER
Datasheet

Specifications of NSYCCOTHC

Body Colour
Light Grey
External Height - Metric
60mm
External Width - Metric
33mm
External Depth - Metric
43mm
Body Material
Thermoplastic
Colour
Light Grey
External Depth
43mm
External Height
60mm
Enclosure Material
Thermoplastic
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
ClimaSys CC
8/92
Thermal control
Overview
Adjustable thermostats
Double-adjustable thermostat
The new quick-fixing systems:
NO (blue button) with normally open contact to control the starting of a fan when
the temperature exceeds the displayed maximum value.
NC (red button) with normally closed contact to control the stopping of a
resistance heater when the temperature exceeds the displayed value.
Large range of temperature control.
Small dimensions.
Easily accessible terminals.
High connection power.
4 types of fixings (novelty).
Double temperature control with a resistance heater and a fan with separate
operation.
Red button: with normally closed contact (NC) for controlling the resistance
heaters.
Blue button: with normally open contact (NO) for controlling the fans.
A double thermostat with separate adjustments and operations within the same
device.
Easily accessible terminals.
Different installation methods.
On 35-mm DIN rail.
On Spacial upright.
On cross-rail.
On mounting plate.

NSYCCOTHC Summary of contents

Page 1

ClimaSys CC 8/92 Thermal control Overview Adjustable thermostats NO (blue button) with normally open contact to control the starting of a fan when the temperature exceeds the displayed maximum value. NC (red button) with normally closed contact to control the ...

Page 2

ClimaSys CC Thermal control Overview Thermostat with NO/NC contact NO/NC inverter for controlling the resistance heaters or the fans. Switching by means of two NO/NC contacts. Easily accessible terminals. High connection power. 4 types of quick-fixing systems. Versions in °C ...

Page 3

... Display Contact Application Control element °C Heat or Inverse Bimetal ventilate °F Interrupting capacity Reference (resistive load NSYCCOTHC 120 V AC NSYCCOTHCF 250 V AC Interrupting capacity Reference (resistive load NSYCCOTHO 120 V AC NSYCCOTHOF 250 V AC Interrupting capacity Reference (resistive load NSYCCOTHD 120 V AC NSYCCOTHDF 250 V AC ...

Page 4

Setting range Display +5 °C…+50 °C °C or °F 7 different operating modes. Electronic thermostat Option of installing one or two external sensors. Setting range Display +5 °C…+50 °C °C or °F 3 different operating modes. Electronic hygrotherm Option of ...

Page 5

... Mounting By clip on 35-mm DIN rail Enclosure UL94 V0 plastic, light grey Dimensions Weight 40 g Mounting position Indifferent Operating –20...+80 °C (–4...+176 °F) temperature Protection rating IP 20 Hysteresis 7 °K Temperature 0...+60 °C setting range Load 2 > Load = resistance Reference NSYCCOTHC NSYCCOTHCF = 0.6) ...

Page 6

Thermal control Thermostat with NO contact to control the starting fan when the temperature exceeds the displayed maximum value. It can control the temperature inside the enclosure by only starting up the fan when necessary, thus increasing ...

Page 7

Thermal control Thermostat (contact adapted to control fans, resistance heaters, ventilation drawers, heat exchangers, etc). Signals and controls the temperature inside the enclosure. Fixing on a DIN rail. Protection rating: IP 20. PC plastic material, self-extinguishing according to standard ...

Page 8

Thermal control Double thermostat: two thermostats in a single device with separate adjustment and operation. – Red button: with normally closed contact (NC) for controlling the resistance heaters. – Blue button: with normally open contact (NO) for controlling the fans, ...

Page 9

Thermal control Electronic temperature controller. Input voltages: 9-30 V, 110-127 V and 220-240 V. Thermostats with 2 independent switching relays (ventilation / heating function). Thermostat precision: +/–1.5 °C. Option of installing external PTC sensors, ref. NSYCCAST, for remote reading ...

Page 10

S1 S1ºt ºt S1A S1B C1 NO1 C2 NO2 NO1 C2 NO2 Load (1) = fan/resistance Load (2) = fan/resistance/alarm Thermal control Electronic temperature and humidity controller. Input voltages: 9-30 V, 110-127 ...

Page 11

Thermal control Electronic humidity controller. Input voltages: 110-240 V. Precision: +/- 5% RH, relative humidity. Hygrostat with 2 independent switching relays (ventilation / heating function). PC plastic material, self-extinguishing according to standard UL94 V0. 2 operating modes for RH ...

Page 12

ClimaSys CC 1 Contact pin circuit breaker. 2 Connection to the network. 3 Connection of phase surveillance. 4 Digital switching outputs. 5 Digital inputs (ref. NSY11955 and NSY11958). 6 Alarm inputs (ref. NSY11954 and NSY11956). 7 Connection of a sensor, ...

Page 13

ClimaSys CC 8/104 Thermal control Door contact Monitors door access by means of a magnetic sensor that reacts to any material conducting magnetic flow. Length of cable supplied Maximum cable length Supplied with fixings. Reference NSY11955 ...

Page 14

ClimaSys CC ClimaSys CC Thermal control Sensors Water sensor Detects all liquids that conduct electricity. Sensor covered in araldite, 100% sealed. Usable in temperature range from –20 to +60 °C. Length of cable supplied Dimensions ...

Page 15

ClimaSys CC ClimaSys CC 8/106 Thermal control Sensors Combined temperature/humidity sensor Combines temperature and air humidity sensor functions. Temperature value range: 0° ... +60°. Measurement accuracy: ± 1 °C. Humidity value range: 10 ... 90% relative humidity between 0° and ...