Processing and Connecting Cable/
Conduit
• The following procedures are recommended for mounting and
• To ensure IP67, use OMRON’s SC-@M and Nippon Flex’s
• Recommended cable: UL2464-type cable that is AWG20 to
• If the 1/2-14NPT is used, cover the cable and conduit end with
• Connect the indicator unit after connecting the seven-conductor
• Properly attach and securely tighten the provided conduit cap to
Terminal no.
wiring the indicator unit securely.
ABS-08Pg13.5 and ABS-12 Pg13.5 Connectors.
AWG18 (0.5 to 1.0 mm
sealing tape to ensure IP67. Tighten the connector to a torque of
1.77 to 2.16 N·m.
cable.
the unused conduit opening to the suitable tightening torque when
wiring the D4BL.
23 (21)
24 (22)
E
E
31
12
1
2
Lp (mm)
30±2
35±2
45±2
55±2
65±2
70±2
90±2
2
) in size and has seven conductors
Lv (mm)
80±2
75±2
60±2
50±2
45±2
35±2
50±2
a (mm)
8±1
Cable Connection Example
1. Connect the wires to the terminals in the order shown below for
2. The insulation sheath of the seven-conductor cable must come into
Others
Do not touch the solenoid because the solenoid radiates heat while
power is being supplied.
wiring efficiency.
Tighten each wired terminal clockwise to a torque of 0.59 to
0.78 N·m.
Twist the wire two or three times and make sure that no bare wire
exists outside the terminal when tightening the terminal.
contact with the wall of the conduit mouth, side A or side B.
Insulation sheath edge
D4BL
15