256-TWMU-QQHG-C6-SS TE Connectivity, 256-TWMU-QQHG-C6-SS Datasheet

TRANSDUCER, WATT, 400HZ, CURRENT

256-TWMU-QQHG-C6-SS

Manufacturer Part Number
256-TWMU-QQHG-C6-SS
Description
TRANSDUCER, WATT, 400HZ, CURRENT
Manufacturer
TE Connectivity
Datasheet

Specifications of 256-TWMU-QQHG-C6-SS

Transducer Function
Watt
Transducer Input Current Ac
5A
Transducer Output Type
Current
Frequency
400Hz
Terminal Type
3-wire
Supply Voltage
120VAC
Input Current
5mA
Power Load Type
Unbalanced
Rohs Compliant
NA
Paladin Transducers 250 Series Class 0.5
Features
Extensive range
High accuracy 0.5%
Up to 3 analogue outputs in one
housing
Zero and span adjustments
DIN rail mounting
Single and 3 phase systems
Flame retardant cases
Screw clamp terminals
Benefits
Cost saving remote metering
Reduction of signal levels for ease of
metering
Isolated output for safety
Protection against high voltage and
overload
Applications
Switchgear
Distribution systems
Generator sets
Control panels
Energy management
Building management
Utility power monitoring
Process control
Motor control
Approvals
UL File No: E140758
CSA File No: LR52592
BV File No: 3896H-07425-AO PRSO BV
An extensive range of Class 0.5 transducers providing measurement, isolation
and conversion of electrical parameters into industry standard DC output signals.
The range offers protection against high voltage and overload, and resistance
to vibration in harsh electrical environments. Transducers offer multiple
analogue outputs from one housing, and individual measurement of most
electrical parameters.
Introduction
Crompton transducers can be used for measuring most electrical parameters.
The following transducers can be supplied:
• A.C. and D.C. current and voltage.
• Active, reactive and apparent power.
• Frequency.
• Power Factor and Phase Angle.
• Integrating current for maximum demand indication and Alarm Control.
• Suppressed zero voltage for monitoring a narrow voltage range.
• Tap position on a high voltage transformer.
• Temperature transmitters for thermocouples and resistance thermometer
• Resistance (slidewire) transmitters.
Safety Features
Crompton transducers and transmitters are designed for use in harsh electrical
environments and feature:
• High protection against overload - 20 x rated current for 1 second.
• High degree of mechanical shock and vibration resistance.
• Protection against high voltage.
Application
• Measurement of most electrical parameters.
• Conversion to standard d.c. output signals.
• Outputs suitable for indication, PLC’s.
• For use in Control Cabinets, Switchboards, Motor Control Centres, Generating
Ordering Information
When ordering please specify:
1. Product catalogue number.
2 Current and/or voltage.
3. Frequency.
4. Auxiliary voltage A.C. or D.C.
5. Options e.g. calibration at 30°C.
6. For power products:
7. For slide wire transmitters quote R1, R2 and R3, see page G9.
8. National Specification:
detectors (RTD’s).
Inputs, outputs and power supply are galvanically isolated from one another
(excluding Resistance transmitters).
Sets, Energy Management & Building Management systems.
a. V.T. & C.T. ratios.
b. System configuration i.e. Single Phase, 3 Phase 3 or 4 Wire, balanced or
Indicated by 7th letter of part number.
unbalanced load.
9

Related parts for 256-TWMU-QQHG-C6-SS

256-TWMU-QQHG-C6-SS Summary of contents

Page 1

Paladin Transducers 250 Series Class 0.5 Features Extensive range High accuracy 0. analogue outputs in one housing Zero and span adjustments DIN rail mounting Single and 3 phase systems Flame retardant cases Screw clamp terminals Benefits Cost ...

Page 2

Paladin Transducers 250 Series Class 0.5 Specification Performance Designed to comply with BS6253 part 1, EN60688, IEC688, AS1384 and ANSI. C37. Temperature Range: Storage -20°C to +70°C Operating 0°C to +60°C Calibrated at 23°C Temperature Coefficient: 0.03%/ per °C Humidity ...

Page 3

... Product Code – 3 Phase Current Transducers - 3 D.C. Outputs Input A.C. A.C. Aux Power O/P D. 120V 0/1mA 120V 4/20mA With multiple analogue outputs, do not common the -ve terminals. 11 Catalogue No. Connection Diag. 253-TAA*-LSFA-C6 1 Catalogue No. Connection Diag. 256-TAA-LSFA-C6 47 Catalogue No. Connection Diag. 253-TAL*-LSHG-C6-DG 6 Catalogue No. Connection Diag. 256-TAS*-LSFA-C6-DG 2 256-TAL*-LSHG-C6-DG 2 ...

Page 4

... Time Constant O/P D.C. 1mA 8 Minutes 0/1mA 1mA 15 Minutes 0/1mA 1mA 30 Minutes 0/1mA 12 Catalogue No. Connection Diag. 253-TAR*-LSFA-C6-DG 6 Catalogue No. Connection Diag. 256-TAR*-LSFA-C6-DG 2 Catalogue No. Connection Diag. 253-TAP*-LSFA-C6-DG 8 253-TAN*-LSFA-C6-DG 8 253-TAM*-LSFA-C6-DG 8 Catalogue No. Connection Diag. 253-TDP*-FAFA-DG 4 253-TDN*-FAFA-DG 4 253-TDM*-FAFA-DG 4 ...

Page 5

... Auxiliary Power: Self Powered Outputs: 0/1mA, 0/5mA, 0/10mA and 0/20mA Product Code – Single Phase, Self Powered, 1 D.C. Output Input A.C. Aux Power O/P D.C. 120V 60Hz Self 0/1mA 13 Catalogue No. Connection Diag. 256-TAB*-LSM1-C6-PQ-T3 3 Catalogue No. Connection Diag. 253-TVA*-PQFA-C6 10 ...

Page 6

... Product Code – Single Phase - Suppressed Zero - A.C. Voltage Transducer, Self Powered - 1 D.C. Output Input A.C. A.C.Aux Power O/P D.C. 108 - 132V Self 0/1mA 14 Catalogue No. Connection Diag. 253-TVL*-PQHG-C6-DG 15 Catalogue No. Connection Diag. 256-TVL*-PQHG-C6-DG 11 256-TVS*-PQFA-C6-DG 11 Catalogue No. Connection Diag. 253-TVZ*-A9FA-C6 15 ...

Page 7

... D.C. Output Input A.C. Frequency O/P D.C. 120V 45/55Hz 0/1mA 120V 55/65Hz 0/1mA 120V 45/65Hz 0/1mA 120V 360/440Hz 0/1mA 15 Catalogue No. Connection Diag. 253-TVR*-PQFA-C6-DG 15 Catalogue No. Connection Diag. 256-TVR*-PQFA-C6-DG 11 Catalogue No. Connection Diag. 253-THZ*-PQFA-AG 10 253-THZ*-PQFA-AN 10 253-THZ*-PQFA-AJ 10 253-THZ*-PQFA-BI 10 ...

Page 8

Paladin Transducers 250 Series Class 0.5 Tap Position Transmitter For accurate remote indication of tap position selection on a high voltage transformer. The variable tap position voltage is monitored, a D.C. output produced which is proportional to the tap position. ...

Page 9

Paladin Transducers 250 Series Class 0.5 Linear Integrator Pulsed Output Transducer Typical applications result in pulses proportional to kilowatt-hours, ampere hours, litre-hours etc., depending on the transducer or transmitter used. Accepts inputs in the form of a process signal derived ...

Page 10

... Copper: 2Ω minimum span, 20Ω maximum span Nickel: 20Ω minimum span, 200Ω maximum span 18 Catalogue No. Connection Diag. 256-TTA*-**FA-DG 18 256-TTM*-**FA-DG 18 256-TTV*-**FA-DG 18 256-TTN*-KTFA-DG 18 256-TTC*-TTFA-DG 18 256-TTF*-JTFA-DG 18 Catalogue No. Connection Diag. 253-TRR*-R1FA-DG 17 253-TRR*-R2FA-DG 17 ...

Page 11

... Product Codes – VA Transducer Single Phase 3 Phase 3 Wire Balanced Load 3 Phase 4 Wire Balanced Load 3 Phase 3 Wire Unbalanced Load 3 Phase 4 Wire Unbalanced Load 19 Catalogue Connection No. Diag. 256-TWK 14 256-TWL 19 256-TWH 24 256-TWM 20 256-TWN 35 256-TWS 38 256-TXK 14 256-TXG 34 256-TXH 42 256-TXM 20 256-TXN 40 256-TYK 14 256-TYG 41 256-TYH 42 256-TYM 20 256-TYN 35 ...

Page 12

... Computer users may find the need for a linearising program. Other transducers are available from Crompton Instruments with a linearised output if required. 20 Catalogue Connection No. Diag. 256-TDSU 43 256-TDCU 43 256-TDAU 43 256-TDTU 45 256-TDEU 46 256-TDBU 46 Catalogue Connection No. Diag. 256-TPSU 14 256-TPAU 14 256-TPTU 42 256-TPBU 19 Catalogue Connection No. Diag. 256-TFSU 14 256-TFCU 14 256-TFAU 14 256-TFTU 42 256-TFEU 19 256-TFBU 19 Catalogue Connection No. Diag. 256-TPDU 36 ...

Related keywords