E5CK-AA1-500 Omron Automation, E5CK-AA1-500 Datasheet - Page 3

no-image

E5CK-AA1-500

Manufacturer Part Number
E5CK-AA1-500
Description
Controller; 100 to 240 VAC; 4 to 20, 0 to 20 mA mA; 15 VA; Analog; SPST
Manufacturer
Omron Automation
Type
Processr
Datasheet

Specifications of E5CK-AA1-500

Brand/series
E5CK Series
Contact Form
SPST-NO
Current, Input
4 to 20, 0 to 20 mA mA
Dimensions
58mmW×58mmH×113mmD
Enclosure Rating
IP00, IP20, IP66
Height
1.89 in.
Input Type
Analog
Ip Rating
IP00, IP20, IP66
Length
2.28 in.
Mounting Type
Panel
Number Of Outputs
1
Output Type
Relay
Power Consumption
15 VA
Primary Type
Controller
Standards
UL, CSA, CE
Time, Response
200 ms (Typ.)
Voltage, Input
1 to 5, 0 to 5, 1 to 10
Voltage, Supply
100 to 240 VAC
Width
4.45 in.
Auxiliary Output
Relay — SPST-NO 3 A @ 250 VAC (Standard)
Supply Voltage
100-240 VAC/24 VAC/VDC
Thermocouple Inputs
K, J, T, E, L, U, N, R, S, B, W
Platinum Rtd Input
Pt100 and JPt100
Current Input
4 to 20 mA DC, 0 to 20 mA DC
Voltage Input
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC
Control Output
SPST-NO 3 A @ 250 VAC/SSR 1 A @ 75 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
J Characteristics
Note: Indication Accuracy --
Indication accuracy (See Note)
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Enclosure ratings
Memory protection
Weight
EMC
Standards - - Approvals
g
Of the K1, T, and N thermocouples at a temperature of -100°C or less: ±2°C ±1 digit maximum.
Of the U, L1, and L2 thermocouples at any temperature: ±2°C ±1 digit maximum.
Of the B thermocouple at a temperature of 400°C or less: unrestricted.
Of the R and S thermocouples at a temperature of 200°C or less: ±3°C ±1 digit maximum.
Of the W thermocouple at any temperature: ±0.3% of the indicated value or ±3°C, (whichever is greater) ±1 digit maximum.
Of the PLII thermocouple at any temperature: ±0.3% or ±2°C, whichever is greater ±1 digit maximum.
g
Temperature
input
Analog
input
Malfunction
Mechanical
Malfunction
Mechanical
Operating
Storage
Operating
Front panel
Rear case
Terminals
E5AK
E5EK
Mounting
bracket
E5CK
Adapter
Thermocouple:
±0.3% of indication value or ±1°C, whichever is greater, ±1 digit max.
Platinum resistance thermometer:
±0.2% of indication value or ±0.8°C, whichever is greater, ±1 digit max.
Analog input: ±0.2% (of indication value) ±1 digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
250 ms scan rate
100 ms scan rate
200 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
10 to 55 Hz, 10 m/s
10 to 55 Hz, 20 m/s
200 m/s
(100 m/s
300 m/s
(14°F to 122°F )
35% to 85% RH
NEMA 4X for indoor use (equivalent to IP66)
IEC standard IP20
IEC standard IP00
Non-volatile memory (number of writings: 100,000 operations)
Approx. 450 g
Approx. 320 g
Approx. 65 g
Approx. 170 g
Approx. 10 g
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection)
--1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on input type)
--10°C to 55°C (14°F to 131°F ) with no icing; with 3-year warranty period: --10°C to 50°C
--25°C to 65°C (--13°F to 149°F ) with no icing
2
2
2
min. (approx. 20G), 3 times each in 6 directions
min. (approx. 30G), 3 times each in 6 directions
(approx. 10G) applied to the relay)
2
2
(approx. 1G) for 10 min each in X, Y, and Z directions
(approx. 2G) for 2 hrs each in X, Y, and Z directions
Digital Process Controller
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
ENV50140:
ENV50141:
EN61000-4-4: 2 kV power-line (level 3)
8 kV air discharge (level 3)
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900
MHz)
10 V (0.15 to 80 MHz) (level 3)
2 kV I/O signal-line (level 4)
E5 K
5

Related parts for E5CK-AA1-500