E5-148-C2422 Eaton / Control Automation, E5-148-C2422 Datasheet - Page 2

no-image

E5-148-C2422

Manufacturer Part Number
E5-148-C2422
Description
COUNT CONTROL/PRESET COUNTER; TIMER; 2 PRESET LCD COUNT CONTROL; DC PWR 48X48MM
Manufacturer
Eaton / Control Automation
Type
Count Controlr
Datasheet

Specifications of E5-148-C2422

Cut Out, Panel
1/16 DIN
Dimensions
1.89"L×3.4"W×1.89"H
Display Type
LCD
Function
Count Control
Number Of Digits
6
Range, Measurement
–199.999-999.999
Special Features
Output Signals
Voltage, Supply
10 to 30 VDC
Power Supply
90?260 VAC or 10?30 VDC
Count Inputs
2 Count Inputs, 4 Input Modes Are Programmable
Polarity Of The Inputs
Programmable for All Inputs in Common
Input Resistance
Approx. 10 KΩ
Protection
IP65 (From Front)
Lead Free Status / Rohs Status
RoHS Compliant part
Features
Standards and Certifications
PG05400001E
2-Line LCD display
Programmable as impulse counter,
frequency meter or time meter with
sign and zero blanking
Power Supply: 90 – 260V AC or
10 – 30V DC
Batch mode
Display range -199.999 – 999.999
with zero blanking
Easy to operate and set the preset
values via 4 keys
Relay or octocoupler-output
Scaling factor 0.0001 – 9.9999
cRU
CE Marked
1 preset value, 1 output
2 preset values, 2 outputs
®
us Approval
Cat. No. E5-148-C2421
Technical Data and Specifications
Supply Voltage: 10 – 30V DC
with reverse polarity protection;
90 – 260V AC max. 4 VA
Display: 2-line LCD display, 6-digits
Count Inputs: 2 count inputs, 4 input
modes are programmable
Polarity of the Inputs:
Programmable for all inputs in
common
Input Resistance: Approx. 10 k
Count Frequency: 10 kHz via DIP-
switches reducible for INP A and
INP B to 30 Hz (0.7 kHz at input
mode E3 and E4 phase
discriminator), automatic repeat at
900 Hz without losing counts (500 Hz
for input mode E4)
Min. Pulse Duration of the Inputs:
5 mS
Input Sensitivity —
DC Supply Voltages
AC Supply Voltages
Pulse Shape: Variable (Schmitt-
Trigger characteristics)
Output 1: Relay —
Counters, Panel Meters, Tachometers and Timers
Count Control
1/16 DIN LCD Count Control
High: 0.6 x U
Low: 0 – 0.2 x U
High: 12 – 30V DC
Low: 0 – 4V DC
With potential free contact, pro-
grammable as normally open or
normally closed
Switching voltage max.: 250V AC/
125V DC
Switching current max.: 3A
Switching current at DC min.:
30 mA
Switching power at DC: 90W
Switching power at AC max.:
750 VA
B
– 30V DC
B
[VDC]
OR
OR
NPN Optocoupler —
Output 2: Relay —
NPN Optocoupler —
Reaction Time of the Inputs —
Data Retention: Min. 10 years or
1x10
Transmitter Voltage: 24V DC -40%/
±15%. 100 mA at 90 – 250V AC
Ambient Temperature: 32 to 122°F
(0 to 50°C)
Storage Temperature: -13 to 158°F
(-25 to 70°C)
EMC: According to EC EMC directive
89/36/EWG, EN 61 000-6-4/ EN 55011
Class B, EN 61 000-6-2
Protection: IP65 (front)
Weight: Approx. 8.47 oz (240 g), AC
version with relay
With open collector and emitter
switching power 30V DC/15 mA
With potential free contact, pro-
grammable as normally open or
normally closed
Switching voltage max.: 250V AC/
125V DC
Switching current max.: 3A
Switching current at DC min.:
30 mA
Switching power at DC: 90W
Switching power at AC max.:
750 VA
With open collector and emitter
switching power 30V DC/15 mA
Relay: Approx. 7 mS
Optocoupler: Approx. 1 mS
With optional backlight —
24V DC -40% ±15%. 60 mA at
90 – 260V AC
6
memory cycles
39