1 Premium™ module TSX SCY 21601: access to Modbus® serial, on a Premium™ automation platform: Modbus® serial (RTU) master.
2 Cable TSX SCY CM6030.
3 Graphic supervision terminal XBTGT5230: Modbus® serial (RTU) master.
4 Cable XBTZ938 + adaptor XBTZG909.
5 Cables VW3 A83 p6Rpp for Modbus® serial, lengths 1.0 to 9.8 ft (0.3 to 3 m).
6 Modbus® serial splitter box LU9 GC3 for equipment connection.
7 Cables TSX CSA p00 for Modbus® serial, lengths 328 to 1640 ft (100 to 500 m).
8 Compact safety PLCs XPSMF4020/MF4022: Modbus® serial (RTU) slaves, Modbus® TCP/IP server.
9 Programming PC.
10 Graphic supervision terminal XBTGT2130: Modbus® serial (RTU) client.
11 Safety remote I/O modules XPSMF1/2/3.
12 Compact safety PLCs XPSMF3022/3522: Modbus® serial (RTU) slaves, Modbus® TCP/IP server.
13 Modular safety PLC XPSMF60, Modbus® serial (RTU) slaves, Modbus® TCP/IP server.
14 Direct connection cables XPSMCSCY for safety PLCs to Premium™ module TSX SCY 21601, length 1 ft (0.3 m).
15 Connector XPSMFADAPT (RJ45/SUB-D 9-pin male) for connector FB2 or FB3, depending on PLC.
Compatibility with compact and modular safety PLCs
Serial link port
Addressing
Medium
Physical layer
Services
Transmission
Elements
Connection on Modbus® serial (RTU)
Characteristics
Bus type
14
2/66
Other safety
equipment
Ethernet,
Access:
related
15
Functions
Binary transfer rate (bps)
Parity
Stop bit
1
2
13
Number and type
Master/Slave
01
02
03
04
23
15
16
05
06
08
43
Code
6
7
Modbus® serial (RTU)
Ethernet
Safety automation system solutions
Preventa™ safety PLCs
Compact and modular, XPSMF
Communication on network and bus
Modbus® serial (RTU)
XPSMF3022, XPSMF3522
1 x SUB-D 9-pin female (FB3)
Slave
122 slave addresses. Addressing range: 1…247
Shielded twisted pair cable
RS 485
13 Modbus® functions (reading/writing of bits and words, event counters, connection events,
diagnostics, identification)
Modbus® slave
Reading n bits of output
Reading n bits of inputs
Reading n words of output
Reading n words of inputs
Reading/writing variables
Writing bit variables
Writing word variables
Writing 1 bit of output
Writing 1 word of output
Diagnostics
Reading equipment identification
115 200, 76 800, 62 500, 57 600, 38 400, 19 200, 9600, 4800, 2400, 1200, 600, 300.
Default value: 57 600
None. Odd. Even. Default value: even
Standard. 1 stop bit. 2 stop bits. Default value: standard
12
8
11
XPSMF4020,
XPSMF4022
1 x RJ45 (Modbus®)
4
3
11
XPSMFCPU22 (CPU of modular
PLC XPSMF60)
1 x SUB-D 9-pin female (FB2)
9
5
10