JFW100G Lineage Power, JFW100G Datasheet

no-image

JFW100G

Manufacturer Part Number
JFW100G
Description
Manufacturer
Lineage Power
Datasheet
Advance Data Sheet
April 2008
The JFW-Series Power Modules use advanced, surface-
mount technology and deliver high-quality, efficient, compact
dc-dc conversion.
Applications
n
n
n
n
Options
n
n
n
Description
The JFW-Series Power Modules are dc-dc converters
that operate over an input voltage range of 36 Vdc to
75 Vdc and provide a precisely regulated dc output.
The output is fully isolated from the input, allowing ver-
satile polarity configurations and grounding connec-
tions. The modules have maximum power ratings from
25 W to 75 W at typical full-load efficiencies of 75%.
The sealed modules have metal baseplates for excel-
lent thermal performance. Threaded-through holes are
provided for easy mounting or adding a heat sink for
high-temperature applications. Listed above are the
enhanced features for convenience and flexibility in
redundant and/or distributed power applications.
dc-dc Converters; 36 to 75 Vdc Input; 2.5 Vdc Output; 25 W to 75 W
Redundant and/or distributed power architectures
Workstations
Computer equipment
Communications equipment
Heat sinks available for extended operation
Choice of primary remote on/off logic configura-
tions
Delayed current-limit shutdown
JFW050G, JFW075G, JFW100G, JFW150G Power Modules:
Features
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
* ISO is a registered trademark of the International Organization
† UL is a registered trademark of Underwriters Laboratories, Inc.
‡ CSA is a registered trademark of Canadian Standards Assn.
§ VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
** This product is intended for integration into end-use equipment.
for Standardization.
All the required procedures for CE marking of end-use equip-
ment should be followed. (The CE mark is placed on selected
products.)
Small size: 61.0 mm x 57.9 mm x 12.7 mm
(2.40 in. x 2.28 in. x 0.50 in.)
High power density
High efficiency: 75% typical
Low output noise
Constant frequency
Metal baseplate
2:1 input voltage range
Anti-rollback circuit
Overcurrent protection
Current-limit set-point adjustment
Primary and secondary remote on/off
Remote sense
Adjustable output voltage: 60% to 110% of V
Output overvoltage protection
Overvoltage set-point adjustment
Synchronization
Forced load sharing (parallelable)
Parallelable with FW300G1
Output current monitor
Overtemperature protection
Power good signal
Thermal warning signal
Case ground pin
ISO* 9001 Certified manufacturing facilities
UL
Certified, and VDE
Licensed
CE mark meets 73/23/EEC and 93/68/EEC direc-
tives**
1950 Recognized, CSA
§
0805 (EN60950, IEC950)
C22.2 No. 950-95
O, nom

Related parts for JFW100G

JFW100G Summary of contents

Page 1

... Advance Data Sheet April 2008 JFW050G, JFW075G, JFW100G, JFW150G Power Modules: dc-dc Converters Vdc Input; 2.5 Vdc Output The JFW-Series Power Modules use advanced, surface- mount technology and deliver high-quality, efficient, compact dc-dc conversion. Applications Redundant and/or distributed power architectures n Workstations ...

Page 2

... max JFW050G JFW075G JFW100G (See Figure 1.) JFW150G (See Figure 2.) Inrush Transient Input Reflected-ripple Current, Peak-to-peak ( MHz, 12 µH source impedance; see Figure 11.) Input Ripple Rejection (120 Hz) Fusing Considerations CAUTION: This power module is not internally fused. An input line fuse must always be used. ...

Page 3

... Lineage Power (continued) Device Symbol All All All All All All All All JFW050G JFW075G JFW100G JFW150G JFW050G JFW075G JFW100G JFW150G All JFW050G JFW075G JFW100G JFW150G All = 25 °C; tested O, max: All All O, max: All All Min Typ Max V 2.46 2.5 2.54 O, set V 2.4 — 2.6 O — ...

Page 4

... O, clamp, nom 4.00 — 5.00 0.4 — — — — 1 425 — 575 Lineage Power Unit hr g (oz µ rated V O, nom V V µs — kHz ...

Page 5

... Table 4. Feature Specifications (continued) Parameter Output Current Monitor ( max JFW050G JFW075G JFW100G JFW150G Overtemperature Protection (See Figure 21.) Power Good Signal (Open collector output: low level indicates power good.): Output Sink Current (V ð 1 Maximum Voltage High-state Internal Impedance to Ground Thermal Warning Signal (Open collector output ...

Page 6

... The following figures provide typical characteristics for the power modules. The figures are applicable to both on/off configurations. 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0 INPUT VOLTAGE, V Figure 1. Typical JFW100G Input Characteristics at Room Temperature 3.0 2.5 2.0 1.5 1.0 0.5 0 INPUT VOLTAGE, V Figure 2. Typical JFW150G Input Characteristics at Room Temperature 6 6 3.0 2 ...

Page 7

... Converters Vdc Input; 2.5 Vdc Output Characteristic Curves (continued) 77.0 76.0 75.0 74.0 73.0 72.0 71.0 70.0 69.0 68.0 67 OUTPUT CURRENT, I Figure 5. Typical JFW100G Converter Efficiency vs. Output Current at Room Temperature OUTPUT CURRENT, I Figure 6 ...

Page 8

... CURRENT PROBE L TEST V (+) I 33 µF ESR < 0.7 Ω @ 100 kHz V (–) I 8-203 (C).l offsets possible bat- S RESISTIVE 10 µF SCOPE LOAD 8-513 (C).b SENSE(+) CONTACT AND DISTRIBUTION LOSSES V (+) LOAD – – SENSE( ) 8-749 (C) – ⎞ x 100 ⎠ – Lineage Power ...

Page 9

... The power module has extra-low voltage (ELV) outputs when all inputs are ELV. The input to these units provided with a maxi- mum 20 A normal-blow fuse in the ungrounded lead. Lineage Power Feature Descriptions Overcurrent Protection To provide protection in a fault (output overload) condi- tion, the unit is equipped with internal current-limiting circuitry and optional delayed shutdown ...

Page 10

... V (+) I S- ON/OFF I on/off, pri (SECONDARY) ON/OFF (PRIMARY) SENSE(– on/off, pri – V (–) I (–)] – [SENSE(+) – SENSE(–)] ð 0 (+) and V (–) terminals O O (–) at the module. O Lineage Power April 2008 I on/off, sec + V on/off, sec – 8-1398 (C) ...

Page 11

... R = --------- - 2 – adj-down ⎝ ⎠ Δ% The test results for this configuration are displayed in Figure 17. This figure applies to all output voltages. Lineage Power 100k 10k LOAD CONTACT AND 100 DISTRIBUTION LOSSES 0 8-651 (C).h Figure 17. Resistor Selection for Decreased ...

Page 12

... Unused SYNC IN pins should be tied to V SYNC IN pin is not used, the module will operate from its own internal clock. April 2008 4 – ⎛ ⎞ kΩ ov-set ------------------------------------ - = adj ⎝ ⎠ V – 4.3 ov-set (–) pins of the modules must be I (–). If the I Lineage Power ...

Page 13

... Schottky diodes are not needed. An internal anti-rollback circuit prevents either output voltage from falling more than 1 V below the other dur- ing light load operation. Lineage Power Good layout techniques should be observed for noise immunity. To implement forced load sharing, the follow- ing connections must be made: ...

Page 14

... For additional information regarding this module, refer to the Thermal Management JC-, JFC-, JW-, and JFW- Series 150 W Board-Mounted Power Modules Technical Note (TN97-008EPS). April 2008 MEASURE CASE TEMPERATURE HERE 8-1397 (C).a Lineage Power ...

Page 15

... Figure 22. Forced Convection Power Derating with Figure 23. JFW100G Power Dissipation vs. Output 4.0 m/s (800 ft./min 3.5 m/s (700 ft./min 3.0 m/s (600 ft./min 2.5 m/s (500 ft./min 2.0 m/s (400 ft./min 1.5 m/s (300 ft./min 1.0 m/s (200 ft./min 0.5 m/s (100 ft./min 0.1 m/s (NAT. CONV.) (20 ft./min ...

Page 16

... NO HEAT SINK 0.5 1.0 1.5 2.0 (100) (200) (300) (400) AIR VELOCITY, IN m/s (ft./min.) Curves; Either Orientation = 54 V and an output current ° ° using Figure 24 – ----------------------- - – ----------------------- - = 24 = 1.9 °C/W Lineage Power 2.5 3.0 (500) (600) 8-1153 (C).a ...

Page 17

... S P ∅ D θcs Figure 26. Resistance from Case-to-Sink and Sink-to-Ambient Lineage Power For a managed interface using thermal grease or foils, (continued) a value of θcs = 0.1 °C/W to 0.3 °C/W is typical. The solution for heat sink resistance is: (continued) θsa This equation assumes that all dissipated power must be shed by the heat sink ...

Page 18

... PLACES (–OUTPUT AND BRONZE, 10 PLACE +OUTPUT) 2.54 (0.100) 12.7 (0.50) V (-) I CASE SYNC OUT SYNC IN SENSE(–) SENSE(+) TEMPWARN VoTRIM ON/OFF OCTRIM OVTRIM PWRGOOD CURMON PARALLEL S-ON/OFF V (+) I 4.8 (0.19) 48.3 (1.90) April 2008 5.3 (0.21) MIN 7.62 (0.300) MOUNTING INSERTS M3 x 0.5 THROUGH, 4 PLACES V (-) O 35.56 (1.400) 12.70 (0.500) V (+) O Lineage Power 8-1397 (C).b ...

Page 19

... April 2008 dc-dc Converters Vdc Input; 2.5 Vdc Output Recommended Hole Pattern Component-side footprint. Dimensions are in millimeters and (inches). 35.56 (1.400) 5.08 (0.200) 5.08 (0.200) 50.8 (2.00) 12.7 (0.50) Lineage Power 57.9 (2.28) MAX 4.8 48.3 (1.90) (0.19) V (+) I ON/OFF 5.08 (0.200) SYNC IN SYNC OUT CASE 10.16 (0.400) 48.26 (1.900) V (-) I 5.1 (0.20) 2.54 (0.100) MODULE OUTLINE PARALLEL S-ON/OFF ...

Page 20

... Negative 50 W Negative 75 W Negative 25 W Positive 37.5 W Positive 50 W Positive 75 W Positive JFW150G JFW150G1 JFW150G31 Suffix 3 1 — April 2008 Device Comcode Code JFW050G1 TBD JFW075G1 TBD JFW100G1 108336173 JFW150G1 108329285 JFW050G TBD JFW075G TBD JFW100G TBD JFW150G TBD Lineage Power ...

Page 21

... Dimensions are in millimeters and (inches). 1/4 IN. 1/2 IN. 1 IN. 61 (2.4) 1 1/2 IN. 57.9 (2.28) Figure 27. Longitudinal Heat Sink Lineage Power 61 (2.4) 8-2832 (C) Figure 28. Transverse Heat Sink Comcode 407243989 407243997 407244706 407244714 407244722 407244730 407244748 1/4 IN ...

Page 22

... Converters Vdc Input; 2.5 Vdc Output Notes 22 April 2008 Lineage Power ...

Page 23

... April 2008 dc-dc Converters Vdc Input; 2.5 Vdc Output Notes Lineage Power 23 ...

Page 24

... Lineage Power reserves the right to make changes to the produc t(s) or information contained herein without notice. No liability is ass umed as a res ult of their use or applic ation. No rights under any patent acc ompany the sale of any oduct information. ...