CPT-DINAV53HA3AX Carlo Gavazzi Inc., CPT-DINAV53HA3AX Datasheet - Page 3

no-image

CPT-DINAV53HA3AX

Manufacturer Part Number
CPT-DINAV53HA3AX
Description
Energy Management Compact Power Transducer Type Cpt-din ?advanced Version?
Manufacturer
Carlo Gavazzi Inc.
Datasheet
CPT-DIN
Output Specifications (cont.)
RS422/RS485
RS232 Configuration Bus
CptASoft software: parameter programming and data reading
System selection
CptASoft
Software functions
Specifications are subject to change without notice
Connections
Baud-rate
Connections
Addresses
Protocol
Data (bidirectional)
Data format
Baud-rate
Insulation
Data format
Working mode
Programming parameters
System 3, unbalanced
System 3, balanced
System 1, balanced
Dynamic (reading only)
Static (writing only)
System selection: 1-2-3
phases
CT/VT ratios
(on request)
Multidrop
bidirectional (static and
dynamic variables)
2 or 4 wires, max. distance
1200m, termination directly
on the instrument
From 1 to 255,
selectable via software
MODBUS/JBUS (RTU)
System and phase variables:
see table “List of variables...”
All the configuration parameters.
1 start bit, 8 data bit,
no parity,1 stop bit
4800, 9600,
19200, 38400 bits/s
By means of optocouplers,
See table “Insulation
between inputs and outputs”
RJ12 (3-wire) for special cable
4800 bits/s
1 start bit, 8 data bit,
no parity, 1 stop bit
Multi language software to
program the working
parameters of the transducer
and to read the energies and
the instantaneous variables.
Compatibility with Windows
95/98/98SE/2000/XP .
Two different working
modes can be selected:
- management of a local
RS485 network;
- management of the
communication from single
instrument to PC (RS232);
3-phase (3-wire, 4-wire)
3-phase ARON
2-phase (3-wire)
1-phase (2-wire)
3-phase (3-wire, 4-wire)
3-phase (3-wire) “1CT+1VT”
3-phase (3-wire) “1CT+3VT”
3-phase (4-wire) “1CT+1VT”
3-phase (4-wire), phase to
neutral voltage measurement
1-phase (2-wire)
CPT-DINADS110706
RS232
Dupline
Transformer ratio
Filter
Type
Connections
Address
Protocol
Baud-rate
Bus
Address
Variables
Insulation
Insulation
CT
VT (PT)
Operating range
Filtering coefficient
Filter action
Data access
Filtering parameters
Alarm variables
Alarm set-points and rele-
vant parameters
Variables to be connected
to the analogue outputs
Scaling of analogue outputs
Energies to be connected
to the pulse outputs
Parameters related to the
pulse outputs
Reset function: max/min
values, energies, dmd
By means of RS232 serial
port, RS485 serial port or RS232
configuration port (RJ12)
Halfduplex communication
Point to point connection
3-wire, max. distance 15m
1 to 255 selectable via software
MODBUS/JBUS (RTU)
4800, 9600, 19200,
38400 bits/s
other characteristics like
R422/RS485 port
Full Dupline compatibility
Programmable using CptASoft
kWh, kvarh + 8 variables
chosen among the
available ones.
By means of optocouplers.
See table “Insulation
between inputs and outputs”
1 to 60 000
1.0 to 6 000.0
0 to 100% of the
retransmitted scale
1 to 32
Measurements, alarms,
serial output
(fundamental variables: V, A,
By means of optocouplers,
See table “Insulation
between inputs and outputs”
W and their derived ones).
3