rsa6351p Yamatake Corporation, rsa6351p Datasheet - Page 6

no-image

rsa6351p

Manufacturer Part Number
rsa6351p
Description
Single Loop Controller
Manufacturer
Yamatake Corporation
Datasheet
Event
Communica-
tion
Loader
communica-
tion
Current
transformer
input
Event type
Operating differential 0 to 9999 digit
Output operation
Output type
Output rating
Life
Min. opening and
closing specifications
Communication system Communication protocol
Interface
Message characters
Communication line
Transmission speed
Recommended cable Dedicated cable, 2m long
Number of inputs
Detection function
Input object
Measurement current 0.4 to 50A
range
Indication accuracy
Indication range
Indication resolution
Output
Min. detection time
G shows that the ON/
OFF is changed at
this value.
shows that the ON/
OFF is changed at
a point that "1U" is
added to this value.
The direct and reverse action settings are disabled for the timer event.
When using the timer event, it is necessary to set the operation type of the DI allocation to "Timer Start/Stop".
Additionally, when setting the event channel designation of the DI allocation, multiple timer events are
controlled from individual internal contacts (DI).
G Setting items
G Operation specifications
G CAUTION
Direct/Reverse action, standby, and READY operations can be set when setting up each event (E1.C1 to
E5.C2).
ON in RSP mode.
OFF in LSP mode.
ON/OFF operation
5V, 10mA (reference value)
Network
Data flow
Synchronization method
Data line
Communication lines
Transmission speed
Communication distance
Protocol
Data length
Stop bit length
Parity bit
3-wire
2 points
Control output is OFF.: Detection of final control devices short-circuit
QN206A (5.8mm-hole diameter)
QN212A (12mm-hole diameter)
±5%FS±1 digit
0.1A
Final control device short-circuit detection: Min. control output OFF time 0.3s or more
SPST relay contacts, Common for 3 points/independent contact for 2 points
250Vac/30Vdc, 2A (resistive load)
100,000 cycles or more
Transmission system
Character configuration
Fixed at 19200 bps
Control output is ON.: Detection of heater line break or overcurrent
Number of current transformer windings: 800 turns
0.0 to 70.0A
Selected from control output 1 and control output 2, or event output 1, event output 2, and event output 3.
Burnout detection: Min. control output ON time 0.3s or more
• ON delay time: A period of time necessary to change the event from OFF to ON after DI has been
• OFF delay time: A period of time necessary to change the event from ON to OFF after DI has been
• The event is turned ON when DI ON continues for ON delay time or longer.
• The event is turned OFF when DI OFF continues for OFF delay time or longer.
• In other cases, the current status is continued.
When setting the ON delay and OFF delay, it is necessary to put in "Multi-function setup".
The default settings of the ON delay and OFF delay before shipment are 0.0s.
The default setting of the event channel designation of the DI allocation before shipment is "0". In this
case, the timer event start/stop can be set for all internal events from one internal contact (DI).
Additionally, as one or more event channel designation is set, the timer event start/stop can be set for one
internal event specified by one internal contact (DI).
However, when setting the event channel of the DI allocation, it is necessary to put in "Multi-function setup".
changed from OFF to ON.
changed from ON to OFF.
Direct action
Internal event
RS-485
1 to 31 units max.
Half-duplex
Start/stop synchronization
Bit serial
Even parity, odd parity, or non-parity
Multidrop, This device is provided with the slave station function.
Balance (differential) type
3 transmit/receive lines
4800, 9600, 19200, 38400 bps
500m max.
RS-485 (3-wire type)
9 to 12 bits/character
7 or 8 bits
1 or 2 bits
DI
6
Optional
Optional
ON delay
ON
Timer (status)
RSP (status)
OFF delay
OFF in RSP mode.
ON in LSP mode.
ON
Reverse action
Time

Related parts for rsa6351p