Specifications of OMNI900LCD

Power - Rated
900VA / 475W
Ac Outlets
8 (4 UPS, 4 Surge Only)
Features
USB Communication Port, USB Cable
Backup Time - Max Load
4 minutes
Voltage - Output Per Connector
120V
Voltage - Input
120V / 15A
Cord Length
6' (1.83m)
Ac Input Connector
NEMA 5-15P
Connector - Ac Output
NEMA 5-15R
Size
4.80" L x 15.60" W x 10.40" H (121.9mm x 396.2mm x 264.16mm)
Weight
16 lbs (7.3kg)
Ac Output Connector
NEMA 5-15R
Brand/series
OmniSmart™
Capacity
900 VA
Color
Black
Communication
USB
Dimensions
12.00 H × 3.70 W × 7.20 D In.
Input Type
NEMA 5-15P
Length, Cord
6 ft.
Mounting Type
Rack/Tower
Operation
Line-Interactive
Output Type
(8) NEMA 5-15R
Power, Rating
475 W
Time, Backup
3 min.
Voltage, Output
120 VAC
Voltage, Supply
475/900 W/VA
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
TL359
Alarms
Switches
SURGE / NOISE SUPPRESSION
AC surge suppression
AC suppression
response time
Dataline suppression
EMI / RFI AC noise
suppression
PHYSICAL
Shipping weight (lbs)
Shipping weight (kg)
Shipping Dimensions
(HWD/in)
Shipping Dimensions
(HWD/cm)
Unit weight (lbs)
Unit weight (kg)
Unit Dimensions
(HWD/in)
Unit Dimensions
(HWD/cm)
Material of
construction
Form factors
supported
Cooling method
Battery Access
Receptacle Color
ENVIRONMENTAL
Operating
Temperature
Storage Temperature
Relative Humidity
COMMUNICATIONS
Network monitoring
port
WatchDog
compatibility
LINE / BATTERY TRANSFER
Transfer time from
line power to battery
mode
Low voltage transfer
to battery power
High voltage transfer
to battery power
Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Includes 2 front panel switches - one main on/off power switch and one dual function "alarm cancel" / "self test" button
870 joules
Instantaneous
-
Yes
15.7
7.1
10.4 x 15.6 x 4.8
26.4 x 39.6 x 12.2
14.6
6.6
Tower format: 12 x 3.7 x 7.2 / Rackmount Shelf format: 3.7 x 12 x 7.2
Tower format: 30.5 x 9.4 x 18.3 / Rackmount Shelf format 9.4 x 30.5 x 18.3
ABS
Rack/Tower
Convection
Battery access door allows user replacement of UPS batteries
Black
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
USB (HID)
Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft
reboot of application / OS or hard power off/on reboot of connected equipment ideal for unattended kiosk applications
2-4 milliseconds
Switches to battery power as line voltage decreases to 89V or less, switches back to AC mode as line voltage
increases to 94V or higher
Switches to battery mode as line voltage increases to 139V or higher, switches back to AC mode as line voltage
decreases to 135V or lower