SM2200NAFTA Tripp Lite, SM2200NAFTA Datasheet - Page 3

no-image

SM2200NAFTA

Manufacturer Part Number
SM2200NAFTA
Description
UPS 2200VA 1700W 6OUT TOWER
Manufacturer
Tripp Lite
Series
Smart Pro®r
Type
UPSr
Datasheet

Specifications of SM2200NAFTA

Power - Rated
2.2kVA / 1700W
Ac Outlets
6 (UPS)
Features
DB9 Communications
Backup Time - Max Load
11 minutes
Voltage - Output Per Connector
120V
Voltage - Input
120V / 15A
Cord Length
8' (2.44m)
Ac Input Connector
NEMA 5-15P
Connector - Ac Output
NEMA 5-15R
Size
12.50" L x 9.00" W x 17.00" H (317.5mm x 228.6mm x 431.8mm)
Weight
80 lbs (36.3kg)
Ac Output Connector
NEMA 5-15R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Media Lines Protected
-
Input circuit breaker
UPS Input cord length
(ft.)
UPS Input cord length
(m)
Recommended
Electrical Service
BATTERY
Full load runtime
(minutes)
Half load runtime
(minutes)
External battery pack
compatibility
DC system voltage
(VDC)
Battery recharge rate
(included batteries)
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage correction
Undervoltage correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
UPS AC suppression
response time
EMI / RFI AC noise
suppression
PHYSICAL
Installation form factors
supported with included
accessories
Primary form factor
20A
8
2.4
20A 120V
11 min. (1700w)
27 min. (850w)
BP24V28-2U
24
Less than 9 hours from 10% to 90%
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 87 to 140
Input voltages between 127 and 140 are reduced by 12%
Input voltages between 95 and 105 are boosted by 10%
Input voltages between 87 and 94 are boosted by 22%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation; set of 4 rear-panel switches control
system enable and contact closure port inverter shutoff commands
480
Instantaneous
Yes
Tower
Tower
(limit 1);
BP24V70-3U
(multi-pack compatible)