3600-P10-SI-10A E-T-A, 3600-P10-SI-10A Datasheet

no-image

3600-P10-SI-10A

Manufacturer Part Number
3600-P10-SI-10A
Description
CIRC BRKR 10A
Manufacturer
E-T-A
Series
3600r
Datasheet

Specifications of 3600-P10-SI-10A

Breaker Type
Thermal-Magnetic
Voltage
65VDC, 250VAC
Current - Trip (it)
10A
Number Of Poles
1
Actuator Type
Push to Reset
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
3600-P10-SI-10AMP
Q2355240
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE to
EN 60934). Designed for plug-in mounting with E-T-A sockets 17-P10-Si,
23-P10-Si, 63-P10-Si; or panel mounting using E-T-A clips. Featuring
an unprotected shunt tap terminal and optional auxiliary contacts. Type
3900 offers lower internal resistance values and is fitted as standard
with auxiliary contacts and an intermediate reset position in which all
contacts are isolated.
Approved to CBE standard EN 60934 (IEC 60934).
Process control systems, instrumentation, communications systems,
rail vehicles.
Type No.
3600
3900
3600 - P10 - Si -
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Current
rating (A)
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
Issue B
Description
Typical applications
Ordering information
Standard current ratings and typical internal resistance values
standard version with shunt tap terminal -3
low-resistance version
Terminal design
P10
blade terminals 6.3-0.8 (QC .250)
Auxiliary contacts (3900: intermediate position as standard)
Si
Si60
ZR-Si
ZR-Si60
Si3-R
Internal resistance (Ω)
3600
447
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
with blade terminals 6.3-08,one each NO/NC,
special auxiliary contact (only 3900)
1 NO, closed in the intermediate and ON position
auxiliary contacts with intermediate position (only 3600)
special auxiliary contact (only 3600)
1 NO, closed in the intermediate and ON position
special auxiliary contacts, 2 NC contacts with reset
button (not approved)
Current ratings
0.05...16 A
0.05...10 A
10 A
Thermal-Magnetic Circuit Breakers 3600/3900
3900
211
48
12.4
5.4
3.1
2.0
1.32
0.76
0.49
0.21
0.101
0.078
ordering example
(type 3600)
(type 3900)
Current
rating (A)
3
4
5
6
7
8
10
12
14
15
16
Internal resistance (Ω)
3600
0.19
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
0.054
0.035
0.025
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
3900
www.e-t-a.com
Current rating range
Dielectric strength
(IEC 60664 and 60664A)
Interrupting capacity
Degree of protection
Humidity
For further details please see chapter: Technical Information
Voltage rating
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
Insulation resistance
Interrupting capacity I
(UL 1077)
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Mass
Authority
3600:
VDE (EN 60934)
CSA/UL
UL
3900:
VDE (EN 60934)
Technical data
Approvals
operating area
main/aux. circuit
aux. circuit 4-5/6-7
type 3600:
standard type
cn
3600
Voltage ratings
AC 240 V; DC 65 V
AC 250 V; DC 80 V
DC 65 V
AC 240 V; DC 65 V
test voltage
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 65 V)
3600: 0.05...16 A
3900: 0.05...10 A
1 A, AC 240 V / DC 65 V
5,000 operations at 1 x I
5,000 operations at 2 x I
-30...+60 °C (-22...+140 °F)
rated impulse
withstand voltage
2.5 kV
reinforced insulation in operating area
AC 3,000 V
AC 1,500 V
AC 840 V
>100 MΩ (DC 500 V)
3600
0.05...0.8 A
1...2 A
2.5...16 A
I
0.05...16 A
0.05...16 A
operating area IP40
terminal area IP00
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms) to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 45 g
N
3900
low-resistance type
3900
0.05...0.2 A self-limiting
0.3...2 A
2.5...10 A
U
AC 250 V
DC 80 V
N
Current ratings
0.05...16 A
0.05...16 A
0.05...25 A
0.05...10 A
pollution
degree
2
N
N
, inductive
, resistive
200 A
400 A
1,000 A
1,000 A
2 - 57
2

Related parts for 3600-P10-SI-10A

3600-P10-SI-10A Summary of contents

Page 1

... NO/NC, Si60 special auxiliary contact (only 3900) 1 NO, closed in the intermediate and ON position ZR-Si auxiliary contacts with intermediate position (only 3600) ZR-Si60 special auxiliary contact (only 3600) 1 NO, closed in the intermediate and ON position Si3-R special auxiliary contacts contacts with reset ...

Page 2

... OFF position blade terminals line 1 DIN 46244-A6.3-0.8 (QC .250 > 2 Terminal design -P10 12.5 This is a metric design and millimeter dimensions take precedence ( mm ) .492 www.e-t-a.com with shunt terminal (standard) and auxiliary contacts (-Si) only 3600 line > 3 (from (from ...

Page 3

... Modular power distribution system for circuit breakers 2210-S, 3600 or 3900. For technical details see product group 7. Power-D-Box with sockets accommodating E-T-A thermal-magnetic circuit breakers type 3600-P10-Si or 3900-P10-Si. For technical data see product group 7. Issue B Typical time/current characteristics 3600 8 … 10000 1000 100 10 1 0.1 0.01 ...

Page 4

... Thermal-Magnetic Circuit Breakers 3600/3900 Sockets 17-P10-Si ( max. load) Retaining clip Y 300 581 11 to special order. slot fitting labels from Phoenix, Weidmüller -P10 6.3 depth .248 10 mm (.394 in.) 2( 2(i) 80 3.15 symmetrical rail EN 50022-35x7.5 polarization recess Sockets 17-P70-Si ( max. load) Retaining clip Y 300 581 11 to special order. ...

Related keywords