W28-SQ11A-10 Tyco Electronics, W28-SQ11A-10 Datasheet

no-image

W28-SQ11A-10

Manufacturer Part Number
W28-SQ11A-10
Description
CIRCUIT BREAK 10A W/SWITCH
Manufacturer
Tyco Electronics
Series
W28r
Datasheets

Specifications of W28-SQ11A-10

Mounting Type
Panel Mount
Breaker Type
Thermal
Voltage
32VDC, 250VAC
Current - Trip (it)
10A
Number Of Poles
1
Actuator Type
Push to Reset
Voltage Rating Vdc
32V
Voltage Rating Vac
250V
Current Rating
10A
No. Of Poles
1
Voltage Ac
250V
Lead Free Status / RoHS Status
Lead free / RoHS non-compliant
Other names
1393250-6
PB236
Features
• Switchable version combines on-off switch and circuit protection in a
• Approved to many international standards (push to reset type).
• Replaces SLOW-BLOW glass cartridge fuse.
• Labor-saving snap-in mounting.
• Button extends for visual trip indication on push to reset model.
• Rocker on switchable model moves to “overload” position upon trip.
Time vs. Current Trip Curve @ +25°C
Electrical Data @ 25°C
Calibration: Will continuously carry 100% of rating.
Dielectric Strength: Over 1,500 volts RMS.
Maximum Operating Voltages: 32VDC; 250VAC, 50/60 Hz.
Interrupt Capacity: 1,000 amps at 250VAC, 50/60 Hz. and 32VDC in
Agency Approvals
W28-X series is UL 1077 Recognized as Supplementary Protectors, File
E69543, and CSA Certified as Appliance Component Protectors, File
LR15734. W28-X breakers (up through 15 amps) are VDE approved for
use in office equipment and provide 8mm isolation.
W28-S is UL 1077 Recognized, and CSA Certified for models up to and
including 15 amps.
single unit.
Switch/Breaker
1000
900
800
700
600
500
400
300
200
100
175
135
0
.1
3-20 amp models – may trip between 101% and 134%, but
must trip at 135% of rating within one hour at +25°C.
0.25-2 amp models – may trip between 101% and 174%, but
must trip at 175% of rating within one hour at +25°C.
(A)
accordance with UL standard 1077 .
1
Push-to-Reset Breaker
Time In Seconds
10
(A) All 3-20 Amp Models
(B)
Overload
1000%
100%
135%
200%
400%
600%
800%
0.17-0.45 Sec.
Trip in 1 hour
2.2-15.0 Sec.
0.55-1.8 Sec.
0.27-0.7 Sec.
0.12-0.3 Sec.
Trip Times
No Trip
100
(B) All 0.25-2 Amp Models
Overload
100%
175%
200%
400%
600%
Users should thoroughly review the technical data before selecting a
product part number. It is recommended that users also seek out the
pertinent approvals files of the agencies/laboratories and review them
to ensure a product meets the requirements for a given application.
Resettable Overload Capacity: Six times rated current for 0.25 through 2
Reset Time: 180 seconds max. for 0.25 through 2 amp models. 10 to 60
Mechanical/Environmental Data
Typical Resistance vs. Current Rating @ +25° C
Endurance Cycling(switchable type): > 6,000 cycles at 100% of rating or
Termination: .250” (6.35mm) quick connects. Soldering to terminals is
Mounting: Snaps into panel from front. See Recommended Panel Cutouts.
Approximate Weight: 0.35 oz. (10g).
W28
Switchable or
Push to Reset
Fuseholder-Type
Thermal Circuit Breaker
Note: VDE not available on 16A and 20A W28
in Amps
Current
Rating
Trip in 1 hour
4.5-28.0 Sec.
1.0-6.5 Sec.
0.4-4.0 Sec.
Trip Times
0.25
0.50
0.75
1.0
2.0
3.0
4.0
5.0
6.0
7 .0
No Trip
seconds for 3 through 20 amp models.
series
not recommended.
1000
Resistance
in Ohms
Typical
To use this chart: Read up from the ambient
temperature to the curve, and across to find a
correction factor. Multiply the breaker rating by the
correction factor to determine the compensated
rating. Calculate the overloads in terms of the
compensated rating to use the published trip curve.
Do not use these devices outside their specified
operating temperature ranges.
Ambient Compensation Chart
14.0
3.55
2.0
0.89
0.17
0.069
0.043
0.030
0.026
0.017
1.40
1.40
1.30
1.30
1.20
1.20
1.10
1.10
1.00
1.00
0.90
0.90
0.80
0.80
0.70
0.70
0.60
0.60
Ambient Temperature In Degrees Centigrade ( C)
Ambient Temperature In Degrees Centigrade ( C)
Dotted portion applies to W28X type only.
amp models. Ten times rated current for
3 through 20 amp models.
–20 –10 0
–20 –10 0
10,000 mechanical cycles.
in Amps
Current
Rating
20.0
10.0
12.0
13.0
14.0
15.0
16.0
11.0
8.0
9.0
10 20 30 40 50 60
10 20 30 40 50 60
Resistance
in Ohms
Typical
0.016
0.014
0.011
0.01
0.009
0.009
0.007
0.007
0.007
0.006

Related parts for W28-SQ11A-10

W28-SQ11A-10 Summary of contents

Page 1

... E69543, and CSA Certified as Appliance Component Protectors, File LR15734. W28-X breakers (up through 15 amps) are VDE approved for use in office equipment and provide 8mm isolation. W28 1077 Recognized, and CSA Certified for models up to and including 15 amps. Electrical Data @ 25°C Calibration: Will continuously carry 100% of rating. ...

Page 2

... QUICK CONNECT TERMINALS .970 DIA. (25.64) 55-025B INTERNAL TOOTH PUSH-ON LOCKWASHER For panels greater than .105” (2.67) thickness Tyco Electronics Corporation Harrisburg, PA 17105 B W Typical Part Number † Not available with Circuit Function “S” . Consult factory for other bezel colors. ...

Related keywords