INTRODUCTION
The LineGard™ 30 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products. The unique design offers the flexibility of splicing in protection of a GFCI
anywhere within the length of the circuit run, making it ideal for both new and existing applications. Unlike breaker style GFCI’s which
have limitations of circuit length from the service panel, the PFGS series can be integrated directly into a circuit or paired in tandem
with an approved receptacle and enclosure.
Available with an operating voltage of 120/240 VAC dual voltage, 3Ø 120/208 VAC, 3Ø 240 VAC (certified to CSA 22.2 only), 3Ø 208 VAC or
3Ø 277 VAC (UL 1053 compliant), all units have 18” splicing leads and a 3/4” NPT fitting to allow connection to 3/4” PVC, EMT, burial and
flexible conduits. All units are MADE IN THE USA and are listed per UL 943 and CSA 22.2 No.144
FeaTUReS
• Power and fault status indicators
• Double insulated user interface
• Industrial design for rough service
• Chemical and UV resistant enclosure
• cULus Listed as a Class A GFCI per UL 943 and
• 30 amp configurations in 120/240 VAC 4-wire,
• NEMA 4X and 6P wet location rated (indoor / outdoor)
• Available in automatic or manual reset configurations
CSA 22.2 No. 144
3Ø 120/208 VAC 5-wire, 3Ø 240 VAC 4-wire,
3Ø 208 VAC 4-wire, 3Ø 277 VAC 4-wire (UL 1053)
PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series
30 Amp Multi-Phase Permanent Series (Splice-In) GFCI
1
1. Manual configuration should be specified if automatic start-up after power
2. Applicable models only
SPeCIFICaTIONS
restoration of circuit power creates an unsafe condition.
Grounded Neutral Protection Trips if ground and neutral touch
Operating Voltage Range 85% to 110% of rated VAC
Open Neutral Protection Trips upon loss of neutral
Operating Temperature –35°C to 66°C
PGFS Series
Rated Supply Voltage 120/240 VAC Dual Voltage,
Operating Frequency 60 Hz
Response Time 25mS max
Let-Go Voltage 60% of supply voltage
Rated Current Up to 30 Amps or rating of wiring
Horse Power 1HP@120 VAC, 3HP@240 VAC
Listing Type cULus Listed Class A
Reset Type
Trip Level 5mA +/–1mA
Phase Dual voltage and 3 phase
1
UL 943
CSA 22.2 No. 144
120/208 VAC 3Ø, 240 VAC 3Ø
(CSA only), 208 VAC 3Ø,
277 VAC 3Ø (UL 1053)
device and/or cable
Automatic or Manual
at load side
http://airpax.sensata.com/

Related parts for PGFS-13105

PGFS-13105 Summary of contents

Page 1

... VAC 4-wire, 3Ø 277 VAC 4-wire (UL 1053) • NEMA 4X and 6P wet location rated (indoor / outdoor) • Available in automatic or manual reset configurations 231 PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series PGFS Series 30 Amp Multi-Phase Permanent Series (Splice-In) GFCI SPeCIFICaTIONS Rated Supply Voltage 120/240 VAC Dual Voltage, ...

Page 2

... Submersible pumps Pipeline heaters Automotive garages Industrial part washers outdoor signage De-icing equipment (roof heaters) PGFS - Ampacity 4 Reset Type 3 30 amps 0 Manual 1 Automatic Flying Leads (Splice-in) PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series 6 Mounting Type 5 Panel mount 5 Fault Output Options 0 None 232 ...

Page 3

This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011 BUSINeSS CeNTeRS Sensata Technologies 807 Woods Road Cambridge, MD 21613, UsA phone: +1 410-228-1500 Brands: Airpax™ Sensata Technologies Inc. 529 Pleasant Street Attleboro, MA 02703, ...

Related keywords