1605000 Phoenix Contact, 1605000 Datasheet - Page 2

HEAVYCON INSERT MODULE ML 2POS

1605000

Manufacturer Part Number
1605000
Description
HEAVYCON INSERT MODULE ML 2POS
Manufacturer
Phoenix Contact
Series
HEAVYCON® Mr
Datasheet

Specifications of 1605000

Connector Type
Module
Gender
Male
Number Of Positions
2
Termination Style
Screw
Voltage Rating
600V
Current Rating
100A
Contact Plating
Silver
Insert / Contact Gender
Male
Number Of Positions / Contacts
2
Product Type
Inserts
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Size
-
Contact Type
-
Lead Free Status / Rohs Status
 Details
Other names
HC-M-HS-MOD-ST
HC-M-HS-MOD-ST
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1605000
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Rated voltage (III/3)
Rated current
Rated surge voltage
Ambient temperature (operation)
Number of positions
Mechanical characteristics
Conductor cross-section
Connection cross-section AWG
Stripping length of the individual wire
Tightening torque
Wire diameter including insulation
Hexagonal socket
Insertion/withdrawal cycles
General characteristics
Number of module slots
Connection method
Inflammability class acc. to UL 94
Pollution degree
Surge voltage category
Assembly instructions
Connection
Order No.: 1605000
1000 V
100 A
8 kV
-40 °C ... 125 °C
2
16 mm² ... 35 mm²
4 ... 2
13 mm
6 Nm (16 mm
7 Nm (25 mm
8 Nm (35 mm
11.4 mm
SW 4
≥ 500
2
Axial screw connection
V0
3
III
- Use HC housing h >= 72 mm- Connection of wires using a 4
mm Allen wrench- Axial screw connection only for stranded wires-
Plug-in connections may only be operated only when there is no
load/voltage
Note for axial connection method The specified conductor
cross-sections refer to the geometric cross-section of the used
conductor.The use of conductors with a geometric cross-
section that deviates greatly from the nominal cross-section
of the conductor should be checked first.The wiring space of
the axial screw technology has been designed for fine strand
conductors as per VDE 0295 class 5. Deviating conductor
superstructures (e.g. class 6 conductors) must be checked before
use.Connection It must be ensured before installation that the
ball screw is completely turned back (chamber is open). Twisting
the conductors is not allowed. The cores must be pushed up to
the end of the contact chamber (until the contact is insulated).
Keep the core in this position and tighten it using an Allen key.
The required core end must be cut before a reconnection.
Tightening the connection screw is allowed only once in order to
prevent a breakage of the litz wire.
2