MY4-AC220-240S Omron, MY4-AC220-240S Datasheet - Page 3

General Purpose / Industrial Relays 4PDT 5A 220-240VAC

MY4-AC220-240S

Manufacturer Part Number
MY4-AC220-240S
Description
General Purpose / Industrial Relays 4PDT 5A 220-240VAC
Manufacturer
Omron
Series
MYr
Datasheet

Specifications of MY4-AC220-240S

Contact Form
4PDT
Coil Voltage
220 VAC / 240 VAC
Contact Rating
5 A
Contact Termination
Solder Terminal
Mounting Style
Socket
Power Consumption
0.9 VA to 1.1 VA
Contact Material
Silver with Gold Flash
Coil Current
4.2 mA, 4.6 mA
Coil Type
Standard
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
220/240ACS MY4 MY4220240ACS,
■ Characteristics
Note: The values given above are initial values.
■ Life Expectancy Characteristics
■ Approved Standards
VDE, UL, CSA, IMQ, CE
■ Precautions
Connections
Do not reverse polarity when connecting DC-operated Relays with
built-in diodes or indicators or high-sensitivity DC-operated Relays.
Mounting
Whenever possible, mount Relays so that it is not subject to vibration
or shock in the same direction as that of contact movement.
Contact resistance
Operate time
Release time
Max. operating frequency
Insulation resistance
Dielectric withstand voltage
Vibration resistance
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
Weight
Pole
2-pole
4-pole
4-pole (bifurcated)
Mechanical life
(at 18,000 operations/hr)
AC:50,000,000 operations min.
DC:100,000,000 operations min.
20,000,000 operations min.
Mechanical 18,000 operations/hr
Electrical
Operating
Operating
100 mΩ max.
20 ms max.
20 ms max.
1,800 operations/hr (under rated load)
1,000 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Destruction:10 to 55 Hz, 1.0 mm double amplitude
Malfunction:10 to 55 Hz, 1.0 mm double amplitude
Destruction:1,000 m/s
Malfunction:200 m/s
See the following table.
-55°C to 70°C (-67°F to 158°F) with no icing (see note)
5% to 85% RH
Approx. 35 g
2
(approx. 20G)
2
(approx. 100G)
Electrical life
(at 1,800 operations/hr under rated load)
500,000 operations min.
200,000 operations min.
100,000 operations min.
General-purpose Relay
MY