E2K-C25MY1 Omron, E2K-C25MY1 Datasheet - Page 7

Proximity Sensors CAPACITIVE DC SCR-NO

E2K-C25MY1

Manufacturer Part Number
E2K-C25MY1
Description
Proximity Sensors CAPACITIVE DC SCR-NO
Manufacturer
Omron
Type
Proximity Sensorr
Series
E2K-Cr
Datasheets

Specifications of E2K-C25MY1

Maximum Operating Temperature
+ 70 C
Supply Voltage
12 VDC to 24 VDC
Supply Current
2 mA
Output Voltage
2 V
Operating Supply Voltage
90 VAC to 250 VAC
Mounting Style
Bracket
Minimum Operating Temperature
- 25 C
Current Rating
200 mA
Features
Permits non-contact detection of metallic and non-metallic objects, mounting bracket included
Voltage Rating
200 VAC
Sensing Distance
3 mm to 25 mm
Switch Terminals
Cable
Sensing Face Diameter
34mm
Supply Voltage Min
90VAC
Sensor Output
SCR, NO
Sensor Housing
Cylindrical
Sensing Range Min
0.12"
Sensor Input
Capacitive
Output Type
Transistor
Sensor Type
Capacitive
Sensing Object
Metallic and Non-Metallic
Response Frequency
10Hz
Material - Body
ABS/PC
Shielding
Unshielded
Voltage - Supply
90 VAC ~ 250 VAC
Terminal Type
2-Wire
Package / Case
Cylinder
Sensing Range Max
25mm
Supply Voltage Max
250VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
E2K-C25MY1
Manufacturer:
OMRON
Quantity:
1 000
Safety Precautions
Refer to Warranty and Limitations of Liability.
This product is not designed or rated for ensuring
safety of persons either directly or indirectly.
Do not use it for such purposes.
Do not use this product under ambient conditions that exceed the
ratings.
● Design
Influence of Surrounding Metal
When mounting a Proximity Sensor, be sure to provide a distance of
80 mm min. from surrounding metal objects to prevent the Sensor
from being affected by metal objects other than the sensing object.
When mounting the Sensor with the L-shaped Mounting Bracket, be
sure to provide a distance of 20 mm min. between the face of the
sensing head and the Mounting Bracket.
Mutual Interference
When installing Sensors face-to-face or side-by-side, ensure that the
minimum distances given in the following table are maintained.
Mutual Interference
Model
E2K-C25M@@
E2K-C20M@@
Be sure to
ground.
Face-to-face Mounting
20 mm min.
Dimension
Precautions for Correct Use
Metal
Sensing
surface
80 mm min.
A
(Unit: mm)
100
A
WARNING
100
105
B
80 mm
min.
Parallel Mounting
B
80 mm
min.
80 mm
min.
Effects of a High-frequency Electromagnetic Field
The E2K-C may malfunction if there is an ultrasonic washer, high-
frequency generator, transceiver, portable telephone or inverter
nearby.
For major measures, refer to Noise of Warranty and Limitations of
Liability for Photoelectric Sensors.
Sensing Objects
Power ON Conditions
Sensing is enabled within 200 ms for the E2K-C20M@@. Design the
system so that the power for the Sensor is turned ON before the
power for the load.
● Miscellaneous
Organic Solvents
The Sensor has a case made of heat-resistant ABS resin or PBT
resin. Be sure that the case is free from organic solvents or solutions
containing organic solvents.
• Sensing Object Material
• Indirect Detection
The E2K-C can detect almost any type of object. The sensing
distance of the E2K-C, however, will vary with the electrical
characteristics of the object, such as the conductance and
inductance of the object, and the water content and capacity of the
object. The maximum sensing distance of the E2K-C will be
obtained if the object is made of grounded metal.
To detect objects in metal containers, each metal container must
have a nonmetallic window.
E2K-C
7