SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (max.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
960W Three Phase Industrial DIN RAIL Power Supply
Note.3
Note.2
DRT-960-24
24V
40A
0 ~ 40A
960W
80mVp-p
24 ~ 28V
200ms, 60ms/400VAC
14ms/400VAC
Three-Phase 340 ~ 550VAC (Dual phase operation possible in connecting L1,L3,FG
47 ~ 63Hz
110
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
105 ~ 125% rated output power
Protection type : Constant current limiting, unit will shut down o/p voltage after 3 sec. , re-power on to recover
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +60
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
Component:
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
122.5Khrs min.
276*125.2*100mm (W*H*D)
3.3Kg; 4pcs/14.2Kg/1.14CUFT
91%
2A/400VAC
COLD START 50A
<3.5mA / 530VAC
1.0%
0.5%
0.5%
0.03%/
5
(0 ~ 50
(TSW1) detect on heatsink of power transistor
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting:
(Refer to output load derating curve)
1.6A/500VAC
I/P-FG:1.5KVAC
MIL-HDBK-217F (25 )
30ms/500VAC at full load
200ms, 60ms/500VAC at full load
O/P-FG:0.5KVAC
85
DRT-960-48
48V
20A
0 ~ 20A
960W
80mVp-p
48 ~ 55V
59 ~ 66V
92%
1.0%
0.5%
0.5%
5
(TSW2) detect on heatsink of power diode
D R T- 9 6 0
Compliance to IEC60068-2-6
Note.5
)
File Name:DRT-960-SPEC 2009-08-24
s e r i e s