AD-155B Mean Well, AD-155B Datasheet

Linear & Switching Power Supplies 27.6V/5A 27.1V/0.5A 151.55W W/UPS Func.

AD-155B

Manufacturer Part Number
AD-155B
Description
Linear & Switching Power Supplies 27.6V/5A 27.1V/0.5A 151.55W W/UPS Func.
Manufacturer
Mean Well
Datasheet

Specifications of AD-155B

Product
Switching
Commercial/medical
Commercial
Output Power Rating
138 W
Input Voltage
88 VAC to 264 VAC, 124 VDC to 370 VDC
Number Of Outputs
2
Output Voltage (channel 1)
27.6 V
Output Current (channel 1)
5 A
Output Voltage (channel 2)
27.1 V
Output Current (channel 2)
0.5 A
Mounting Style
Chassis
Output Type
DC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
AD-155B
Manufacturer:
BOURNS
Quantity:
40 000
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
BATTERY LOW
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
OUTPUT NUMBER
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
155W Single Output with Battery Charger(UPS Function)
Note.3
Note.2
AD-155A
CH1
13.8V
10.5A
0 ~ 11.5A
151.55W
150mVp-p
CH1: 12 ~ 14.5V
1000ms, 90ms/230VAC
24ms/230VAC
88 ~ 264VAC
47 ~ 63Hz
PF>0.92 at full load
2.5A/115VAC
CH1:105 ~ 135%
Protection type : AC Charging Mode : Constant current limiting, recovers automatically after fault condition is removed
CH1:15.87 ~ 18.63V
Protection type : Shut down o/p voltage, re-power on to recover
10V 0.8V
-10 ~ +60
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to
183.3K hrs min.
199*110*50mm (L*W*H)
0.88Kg; 16pcs/15Kg/0.95CUFT
80%
COLD START 20A/115VAC
<1mA / 240VAC
2.0%
0.5%
0.5%
0.03%/
(0 ~ 50 )
(Refer to output load derating curve)
EN61000-4-2,3,4,5,6,8,11; ENV50204,
UPS Mode : Protected by internal fuse
I/P-FG:1.5KVAC
124 ~ 370VDC
1.5A/230VAC
MIL-HDBK-217F (25 )
20ms/115VAC at full load
CH2
13.3V
0.5A
0 ~ 0.5A
--------
--------
--------
--------
CH2:0.51 ~ 0.9A rated output power
2000ms, 90ms/115VAC at full load
40A/230VAC
O/P-FG:0.5KVAC
AD-155B
CH1
27.6V
5A
0 ~ 5.5A
151.55W
150mVp-p
CH1: 24 ~ 29V
19.5V(+1.5V,-1V )
CH1:31.74 ~ 37.26V
84%
1.0%
0.5%
0.5%
EN55024, light industry level, criteria A
CH2
27.1V
0.5A
0 ~ 0.5A
--------
--------
--------
--------
A D - 1 5 5
AD-155C
CH1
54V
2.7A
0 ~ 2.7A
156.5W
240mVp-p
CH1: 48 ~ 58V
39V 2V
CH1:62.1 ~ 72.9V
84%
1.0%
0.5%
0.5%
File Name:AD-155-SPEC 2010-11-29
CH2
53.5V
0.2A
0 ~ 0.5A
--------
--------
--------
--------
s e r i e s

Related parts for AD-155B

AD-155B Summary of contents

Page 1

... EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B (Note 4) HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to MTBF 183.3K hrs min. OTHERS DIMENSION 199*110*50mm (L*W*H) 0.88Kg; 16pcs/15Kg/0.95CUFT PACKING NOTE AD-155B CH2 CH1 13.3V 27. 5.5A 151.55W -------- 150mVp-p CH1 29V 2.0% -------- 1 ...

Page 2

... PFC fosc : 67KHz PWM fosc : 134KHz BAT.CHARGER BACK UP RECTIFIERS & FILTER CONSTANT CURRENT LIMITING & DETECTION CIRCUIT O.V.P. 90 100 120 140 160 180 200 220 INPUT VOLTAGE (V) 60Hz File Name:AD-155-SPEC 2010-11- Unit:mm Assignment Terminal JST SXH-001T-P0.6 or equivalent B+ RESET +V -V +13.8V 240 260 ...