LC1D09BD SQUARE D, LC1D09BD Datasheet - Page 18

no-image

LC1D09BD

Manufacturer Part Number
LC1D09BD
Description
CONTACTOR, 3PST-NO, 24VDC, 20A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D09BD

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
24V
Width
45mm
Relay Terminals
Screw Clamp
Contact Voltage Ac Max
600V
Operating Voltage
600VAC
Switching Power Ac1
1hp
Switching Power Ac3
7.5hp
Switching Current Ac1
25A
Switching Current Ac3
9A
Load Current Inductive
9A
Load Current Resistive
25A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Contactor Selection for Utilization Category AC-3
18
©
2001-2004 Schneider Electric All Rights Reserved
Contactor Selection for Utilization Category AC-3
How to Use the Electrical Life Curves
The contactor electrical life curves on the following pages may be used to estimate the number of make
and break operations a contactor can achieve for a specific application. Compare the application to the
utilization category definitions listed on page 16 and select the appropriate chart. Each chart shows the
Number of Operations in Millions on the Y axis and the Current Broken in Amps on the X axis.
AC-1 The current broken should be the same as the make and maintain current.
AC-3 The current broken should be the same as the full load current rating (FLA) of the motor.
AC-4 The current broken should be the same as the locked rotor current (LRA) or
Once the appropriate chart is selected, find the breaking current of the application on the X axis of the
chart and draw a vertical line. Draw a vertical line at this point. Find the intersection of this vertical line
and the life curve of a particular contactor. At the intersection point read the number of electrical
operations off the Y axis. If longer electrical life is required, continue checking the intersection points
until an acceptable contactor is found.
Operational Current and Power Conforming to IEC (
Maximum Operating Rate in Operating Cycles/Hour
Operational Current and Power Conforming to UL, CSA (
Contactor Size
Max. operational
current (AC-3)
Rated
operational power P
(standard motor
power ratings)
On-load Factor
Contactor Size
Max. operational
current (AC-3)
Rated operational
power P (standard
motor power ratings)
60 Hz
f
k
85%
25%
Depending on the operational power and the on-load factor (
Not UL Listed or CSA Certified.
6 times full-load current of the motor.
220/240 Vac
380/400 Vac
415 Vac
440 Vac
500 Vac
660/690 Vac
1000 Vac
Operational Power
P
0.5 P
P
200/208 Vac
230/240 Vac
460/480 Vac
575/600 Vac
440 Vac
440 Vac
A
kW
kW
kW
kW
kW
kW
kW
A
HP
HP
HP
HP
LC1
LP1
K06
LC1
LP1
K06
6
1.5
1.5
3
3
6
1.5
2.2
2.2
3
3
3
LC1
LC1
K09
LC1
LP1
K09
9
2
3
5
5
9
2.2
4
4
4
4
4
55 °C [131 °F]).
LC1
LP1
K12
LC1
LP1
K12
12
3
3
7.5
10
12
3
5.5
5.5
5.5
4
4
LC1
LP1
D09
LC1
LP1
D09
1200
3000
1800
LC1
LP1
D09
9
2
2
5
7.5
f
9
2.2
4
4
4
5.5
5.5
55°C [131 °F]) for Category AC-3
LC1
LP1
D12
LC1
LP1
D12
1200
3000
1800
LC1
LP1
D12
12
3
3
7.5
10
12
3
5.5
5.5
5.5
7.5
7.5
55°C [131 °F])
LC1
LP1
D18
LC1
LP1
D18
1200
2500
1800
LC1
LP1
D18
18
5
5
10
15
18
10
10
4
7.5
9
9
LC1
LP1
D25
LC1
LP1
D25
1200
2500
1800
LC1
LP1
D25
25
7.5
7.5
15
20
25
11
11
11
15
15
5.5
LC1
LP1
D32
LC1
LP1
D32
1000
2500
1200
LC1
LP1
D32
32
10
10
20
30
32
15
15
15
18.5
18.5
7.5
LC1
D38
LC1
D38
1000
2500
1200
LC1
D38
38
18.5
18.5
18.5
18.5
18.5
9
k
LC1
LP1
D40
LC1
LP1
D40
1000
2500
1200
LC1
LP1
D40
40
10
10
30
30
40
11
18.5
22
22
22
30
22
01/04