Accessories
Table 34-403. Line Side Adapters (C320LSA1 and C320LSA2) —
When to Use Them for U.S. Applications
Reference: Technical Paper AP03402001E.
Note: Line Side Adapters are not required for non-U.S. applications. Most countries outside
of the U.S. classify the MMP as a thermal magnetic circuit breaker.
Table 34-404. Accessories
CA08102001E
SCPD = Short Circuit Protective Device (Circuit Breaker, Fuses).
MMP = Manual Motor Protector.
A308 MMP does not require a Line Side Adapter.
Not Required
Using the in-panel
Main SCPD
Group Installation
Line Side Adapter
Types AM/AE317/357 & AE319/359
Freedom Combination Motor Controller (CMC)
Motor Controllers
IEC Combination
UL 508 Type F Combination
Motor Controller — Only
Upstream Feeder SCPD
required; no dedicated
in-panel Main SCPD for
MMP /Contactor
Description
Line Side Adapter for A307 MMPs
(Required for use with A307 MMPs
only when used as Self-Protected
Manual Combination Starters. Not
required for Group Installation.)
Line Side Adapter for A309 MMPs
(Required for use with A309 MMPs
only when used as Self-Protected
Manual Combination Starters. Not
required for Group Installation.).
Wiring Connector Link
(Electrical and mechanical intercon-
nection between A307 MMP + CE12
Freedom Miniature FVNR/FVR
Contactor)
Wiring Connector Link
(Electrical and mechanical intercon-
nection between A307 MMP + CE15
Freedom 45 mm IEC FVNR Contactor
— Sizes A – F)
Wiring Connector Link
(Electrical and mechanical intercon-
nection between A308 MMP + CE15
Freedom 65 mm IEC FVNR Contactor
— Sizes G – K)
Required
Line Side Adapter
MMP /Contactor
For more information visit: www.eaton.com
IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Types AM/AE317/357, AE318/358, AE319/359 Freedom IEC Combination Motor Controllers
Not required for any application
Types AE318/358
UL 508 Type E Self-protected
Manual Combination Starter —
Only Upstream Feeder SCPD
required; no dedicated in-panel
Main SCPD for MMP
Motor Controllers
IEC Combination
Line Side Adapter
Catalog
Number
C320LSA1
C320LSA2
C320WC25
C320WC45
C320WC65
MMP
Only
Price
U.S. $
Protection in Different Controller
Types
A UL 508 Type E Self-protected Manual
Combination Starter/Motor Controller
consists of a single device having inte-
gral short circuit protection, a main set
of contacts, motor overload protec-
tion, and may also include a UL Listed
Line Side Adapter (see Table 34-403).
This type of controller is a legitimate
short-circuit circuit protective device
and disconnect means for the down-
stream motor. It does require an
upstream feeder short circuit protec-
tive device, but does not require a ded-
icated branch circuit protection or a
disconnect means. A UL 508 Type E
rating means that the unit clears a fault
and does not experience any welding
of the power poles. A UL 508 Type E
self-protected manual motor controller
will remain fully functional should a
short circuit within its ratings occur.
E.g. A307, A308 and A309.
A UL 508 Type F Combination Motor
Controller consists of a UL Listed
Type E Self-protected Manual Combi-
nation Starter/Motor Controller, a UL
Listed Contactor, and possibly a UL
Listed Line Side Adapter (see Table 34-
403). While the UL 508 Type E self-
protected manual motor controller
of this combination motor controller
device is a legitimate short circuit
protective device and disconnect
means for the downstream motor,
the contactor is not “self-protected.”
E.g. AM317 – AE319 and AM357 –
AE359.
In addition, as a complete assembly or
with modular components, the device
may have Type 2 Coordination certifi-
cation. Type 2 Coordination means the
Starter or Controller must exhibit little
or no damage following a major short
circuit fault and should be able to be
returned to proper service without
replacing any parts. E.g. All Freedom
CMCs and MMPs.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1