SW60-360P ALBRIGHT ENGINEERS, SW60-360P Datasheet - Page 6

CONTACTOR, C/O, 12VDC

SW60-360P

Manufacturer Part Number
SW60-360P
Description
CONTACTOR, C/O, 12VDC
Manufacturer
ALBRIGHT ENGINEERS
Datasheet

Specifications of SW60-360P

Operating Voltage
12V
Contacts
SPST-NO
Relay Mounting
Bracket
Coil Voltage Vdc Nom
12V
Svhc
No SVHC (18-Jun-2010)
Contact Configuration
SPST
Contact Current Dc Max
80A
Contact Voltage Dc Max
250V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SW66A
6
Please Note.
Very Important:
Magnetically latched
contactors do not fail safe.
If there is a power failure, or
if the supply to the contactor
coil is broken, the contactor
contacts will not open or
close, ie the contactor will
not change state.
These devices should not
therefore be used in
applications where the failure
of contacts to open or close
could result in a hazardous
situation for persons or
equipment.
S W 6 4 / 6 6
Magnetically Latched PC60, MB60 and SW60
PC60M, MB60M & SW60M
The contactors can be supplied with magnetic latching - one short pulse to
close the main contacts - one short pulse to reopen them again.
The result is a bi-stable device, the coil of which consumes no power except
during the closing and opening strokes, and because there is in effect no
heating of the coil, the contactors can be engineered in the first place with
more powerful coils and springs than with conventional contactors.
Contact ratings and all external dimensions are identical to those of the
equivalent types which have conventionally energised coils.
Similarly all the additional features which are available with the other PC60
and SW60 types can be found with the magnetically latched versions, eg
auxiliary contacts, magnetic blowouts for the main contacts, protected, etc.
For more details of the operation of the “M” versions, please see the Albright publication:
“Power Consumption Reduction for Albright Contactors”.
P C ,
M A G N E T I C A L L Y
M B
Installation
Mounting is by M4 tapped holes in the contactor frame
together with a selection of mounting brackets.
Standard arrangement is for the contactors to be supplied
with two M4 holes on each side of the contactor
frame to allow direct attachment to panels etc.
For other options see left.
Paired Contactors
The contactors can be supplied in assembled pairs with
the appropriate connecting links. In the case of the
SW66, the contactor is configured with links for motor
reversing. The resultant circuit is failsafe so that if
both coils are energised simultaneously, an open
circuit results.
D C
C O N T A C T O R S
&
S W
SW64 & SW66
L A T C H E D
S E R I E S
Dimensions in mm (inches).