COKP05A62 MACROMATIC CONTROLS, COKP05A62 Datasheet - Page 2
COKP05A62
Manufacturer Part Number
COKP05A62
Description
CURRENT MONITORING RELAY, SPDT, 0.5-5A
Manufacturer
MACROMATIC CONTROLS
Series
COr
Datasheet
1.COKP05A62.pdf
(2 pages)
Specifications of COKP05A62
Contact Configuration
SPDT
Power Consumption
5VA
Supply Voltage Max
120VAC
Supply Current Max
5A
Relay Mounting
Plug In
Relay Terminals
8 Pin Octal
Control Voltage
120VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Application Data
Input Voltage Tolerance:
AC Operation:
Load (Burden):
Less than 5VA
Current Settings:
Pick-up:
Drop-out: Fixed at 95% of pick-up setting (COP Series); or
Temperature:
-28
Response Times:
Pick-up:
Drop-out:
Output Contacts:
10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),
1/3HP @ 120/240V AC (N.C.)
Dimensions
1/09
o
to 55
o
Adjustable throughout current range monitored
Adjustable from 50-95% of pick-up setting (COKP
Series)
C (-20
Adjustable 0.1-10 seconds
Fixed 100ms
2.4 (60)
o
+10/-15% of nominal at 50/60 Hz.
to 131
o
F)
1.7 (43)
CURRENT MONITOR RELAYS
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Indicator LED: Green when Input Voltage is applied;
Red when Relay is energized
Reset: Automatic. Contact Macromatic for information
on a product with a latching function--the relay remains
energized even after the current drops below the drop-
out setting until a remote N.C. button is opened.
Mounting:
Requires an 8 or 11 pin octal socket--see page 81.
Approvals:
(74)
2.9
Low Voltage & EMC Directives
EN60947-1, EN60947-5-1
(89)
3.5
File #E109466
CO Series Overcurrent
Application Data & Dimensions
File #E109466
with
appropriate
socket
All dimensions are inches
COKP
(millimeters)
Only
AC Plug-in
23