DIB01CB235A CARLO GAVAZZI, DIB01CB235A Datasheet - Page 3

CURRENT MONITORING RELAY, SPDT, 0.1-5A

DIB01CB235A

Manufacturer Part Number
DIB01CB235A
Description
CURRENT MONITORING RELAY, SPDT, 0.1-5A
Manufacturer
CARLO GAVAZZI
Series
DIB01r
Datasheet

Specifications of DIB01CB235A

Contact Configuration
SPDT
Power Consumption
4VA
Supply Voltage Max
230VAC
Supply Current Max
5A
Relay Mounting
DIN Rail
Control Voltage
230VAC
Leaded Process Compatible
Yes
Carry Current
8A
Features
0.1-5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
DIB01CB235A
Manufacturer:
Carlo gavazzi
Quantity:
500
DIB01, PIB01
Mode of Operation
DIB01 and PIB01 monitor
both AC and DC over or
under current through an
internal shunt.
Example 1
(connection between termi-
nals Z1, Y1 or 8, 9 - latching
function enabled)
The
latches in operating position
when the measured value
Function/Range/Level and Time Delay Setting
Adjust the input range set-
ting the DIP switches 1 and
2 as shown below (except
for
and PIB01xxx10A).
Select the desired function
setting the DIP switches 3 to
6 (1 to 4 for DIB01xxx10A
and PIB01xxx10A) as shown
below.
Specifications are subject to change without notice (06.02.08)
models
relay
operates
DIB01xxx10A
and
exceeds (or drops below)
the set level for more than
the set delay time. Provided
that the current has dropped
below (or has exceeded) the
set point (see hysteresis set-
ting),
when
between terminals Z1, Y1 or
8, 9 is interrupted or the
power supply is interrupted
as well.
The red LED flashes until the
To access the DIP switches
open the grey plastic cover
as shown below.
Relay working mode
ON: Normally De-energized
OFF: Normally Energized
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable
OFF: Inhibit function enable
Monitoring function
ON: Over current
OFF: Under current
10 A Models
the
the
relay
interconnection
releases
delay time has expired or
the measured value comes
back to a non-alarm value
(see hysteresis setting).
Example 2 (Stardard CT)
(no connection between ter-
minals Z1, Y1 or 8, 9 - latch
function disabled)
The relay operates when the
measured value exceeds (or
drops below) the set level for
Selection of level and time
delay:
Upper knob:
Setting of hysteresis on rela-
tive scale: 0 to 30% on set
value.
Other Models
Measuring range
SW1
SW2
5MA
50MA
500MA 100 mA 200 mA 500 mA
5A
Relay working mode
ON: Normally De-energized
OFF: Normally Energized
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable
OFF: Inhibit function enable
Monitoring function
ON: Over current
OFF: Under current
more than the set delay
time. It releases when the
current
exceeds) the set level (see
hysteresis setting) or when
power supply is interrupted.
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
Centre knob:
Current level setting on rela-
tive scale: 10 to 110% on
full scale.
Lower knob:
Setting of delay on alarm
time on absolute scale (0.1
to 30 s).
ON
OFF
1 mA
10 mA
1 A
drops
ON
ON
2 mA
20 mA
2 A
below
OFF
ON
5 mA
50 mA
5 A
(or
3