Specifications of 3UG4622-1AA30

Power Consumption
2W
Supply Voltage Max
26.4V
Relay Mounting
DIN Rail
Contact Termination
Screw
External Depth
86mm
External Length / Height
110mm
External Width
22.5mm
Control
RoHS Compliant
Control Voltage Ac Max
240V
Control Voltage Ac Min
24V
Control Voltage Dc Max
240V
Rohs Compliant
Yes
Control Voltage Dc Min
24V
3UG Monitoring Relays for Electrical and Additional Measurements
Line monitoring
3UG45 13 monitoring relays
The 3UG45 13 line monitoring relay monitors three-phase net-
works with regard to phase sequence, phase failure, phase un-
balance of 20 % and undervoltage. The device has an internal
power supply and works using the closed-circuit principle. The
hysteresis is 5 %. The integrated response delay time is adjust-
able from 0 to 20 s and responds to undervoltage. If the direction
is incorrect, the device switches off immediately. Thanks to a
special measuring method, a phase failure is reliably detected
in spite of the wide voltage range from 160 to 690 V AC and
feedback through the load of up to 80 %. When the mains volt-
age is switched on, the green LED is lit. If the phase sequence
at the terminals L1-L2-L3 is correct, the output relay picks up.
If the phase sequence is wrong, the red LED flashes and the out-
put relay remains in its rest position. If a phase fails, the red LED
is permanently lit and the output relay drops.
Note:
The red LED is a fault diagnostic indicator and does not show the
current relay status. The 3UG45 13 monitoring relay is suitable
for line frequencies of 50/60 Hz.
Phase failure and undervoltage
Wrong phase sequence
7/62
11/14
11/12
21/24
21/22
LED rd
3~U
Monitoring Relays
L1-L2-L3
n
Siemens LV 1 T · 2007
OFF
L2-L3
L3-L2-L1
LED rd
Phase loss
11/14
11/12
21/24
21/22
ON
OFF
L1-L2-L3
Phase sequence
Delay
OFF
FLASH
-20%
OFF
ON
OFF
NSB0_01569
Hysteresis
© Siemens AG 2007
5%
3UG46 14 monitoring relays
The 3UG46 14 line monitoring relay has a wide voltage range
and an internal power supply. The device is equipped with a dis-
play and is parameterized using three buttons. It monitors three-
phase networks with regard to phase unbalance from 5 to 20 %,
phase failure, undervoltage and phase sequence. The hystere-
sis is adjustable from 1 to 20 V. In addition the device has
a response delay and ON-delay from 0 to 20 s in each case.
The integrated response delay time responds to phase unbal-
ance and undervoltage. If the direction is incorrect, the device
switches off immediately. Thanks to a special measuring
method, a phase failure is reliably detected in spite of the wide
voltage range from 160 to 690 V AC and feedback up to 80 %
through the load.
The 3UG46 14 monitoring relay can be operated on the basis of
either the open-circuit or closed-circuit principle and with
manual or auto RESET.
With the closed-circuit principle selected
Wrong phase sequence
Phase failure
Undervoltage
Unbalance
11/14
11/12
21/24
21/22
11/14
11/12
21/24
21/22
x-y
0%
11/14
11/12
21/24
21/22
onDelay
onDelay
L3-L2-L1
L1-L2-L3
11/14
11/12
21/24
21/22
> Asy
<
L2-L3
Delay
Delay
L1-L2-L3
Hysteresis
Hysteresis
2%