Monitoring Relays
1-Phase True RMS AC/DC Over or Under Current
Types DIB02, PIB02
Product Description
DIB02 and PIB02 are precise
TRMS AC/DC over or under
current (selectable by DIP-
switch) monitoring relays.
The current is measured through
an external shunt. 1-phase
and 3-phase current up to
500 AAC can be monitored
connecting MI or MP current
transformers.
Type Selection
Mounting
DIN-rail
Plug-in
Input Specifications
Input
Measuring ranges
Note:
Specifications are subject to change without notice (30.10.03)
DIB02
Voltage level
6 to 60 mV AC/DC
15 to 150 mV AC/DC
Max. voltage for 1 s
0.4 to 4 V
Max. voltage for 1 s
MI and MP CT ranges
The input voltage cannot
raise over 300 VAC/DC with
respect to ground (PIB02 only)
1-ph.:
MI 5
MI 20
MI 100
MI 500
p
AC
Output
SPDT
SPDT
3-ph.:
MP 3005
MP 3020
MP 3100
MP 3500
Supply: 24 VDC
DIB 02 C 724 150MV
PIB 02 C 724 150MV
Owing to the built-in latch
function, the ON-position of
the relay output can be
maintained. Inhibit function
can be used to avoid relay
operation when not desired
(maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay.
PIB02
DIB02: Terminals Y1, Y2
PIB02: Terminals 5, 7
Internal resis.
1 k
1 k
50 k
AAC rms
0.5 to 5 A
2 to 20 A
10 to 100 A
50 to 500 A
Max. curr.
Max. volt.
2 V
2 V
15 V
50 V
100 V
250 AAC
750 AAC
20 AAC
50 AAC
Supply: 48 VDC
DIB 02 C 748 150MV
PIB 02 C 748 150MV
Input Specifications (cont.)
Note:
Contact input
• TRMS AC/DC over or under current
• Current measuring through external shunt or CT
• Selection of measuring range by DIP-switches
• Measuring ranges from 6 to 150 mV AC/DC and
• Adjustable current on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
• 22.5 mm Euronorm housing (DIB02)
• LED indication for relay, alarm and power supply ON
• Galvanically separated power supply
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
Range
MP3... current transformers
not suitable for under cur-
rent measurement due to
the output signal of the
device (see data sheet)
DIB02
PIB02
Disabled
Enabled
Latch disable
monitoring relays
0.4 to 4 V
DIN/EN 50 022 (DIB02) or plug-in module (PIB02)
or 36 mm plug-in module (PIB02)
p
Supply: 24/48 VAC
DIB 02 C B48 150MV
PIB 02 C B48 150MV
AC (MI or MP range)
DIB 02 C B23 150mV
Terminals Z1, Y1
Terminals 8, 9
> 10 k
< 500
> 500 ms
Supply: 115/230 VAC
DIB 02 C B23 150MV
PIB 02 C B23 150MV