VAKP012D MACROMATIC CONTROLS, VAKP012D Datasheet

VOLTAGE MONITORING RELAY, DPDT, 12VDC

VAKP012D

Manufacturer Part Number
VAKP012D
Description
VOLTAGE MONITORING RELAY, DPDT, 12VDC
Manufacturer
MACROMATIC CONTROLS
Series
VAr
Datasheet

Specifications of VAKP012D

Contact Configuration
DPDT
Power Consumption
3VA
Supply Voltage Max
12VDC
Relay Mounting
Plug In
Control Voltage Type
DC
Relay Terminals
8 Pin Octal
Control Voltage
12V
No. Of Poles
2
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
u
u
u
u
u
u
u
30
VOLTAGE MONITOR RELAYS
VA Series Over/Undervoltage
Adjustable Time Delay on Drop-Out
12-120V Plug-in
www.macromatic.com
sales@macromatic.com
800-238-7474
Monitors AC single phase
and DC voltages
Wide range of user-adjust-
able pick-up and drop-out
settings
Adjustable time delay on
drop-out of 0.5 - 10 seconds
LED indicates output relay
status
Compact plug-in case
utilizing industry standard 8
pin octal socket
10A DPDT output contacts
(with appropriate socket)
*
** Drop-out Voltage is adjustable from 75-95% of the adjusted Pick-up Setting.
Sockets & Accessories Pages 81 & 82
Over/Under Voltage Relays provide protection to equipment where an over or under
voltage condition is potentially damaging. They are designed to operate when the
operating voltage reaches a preset value and drop-out when the operating voltage drops
to a level below the preset value.
The pick-up voltage setting is user-
adjustable from 85-115% of the
nominal voltage rating. As
standard, the VAP Series has a
drop-out voltage setting fixed at
95% of the pick-up voltage setting.
An adjustable drop-out setting of
75-95% of the pick-up setting is
available on the VAKP Series. The
relay energizes when the moni-
tored voltage is above the pick-up
setting. The relay de-energizes when the monitored voltage is below the drop-out setting
for a period longer than the drop-out time delay (T), which is adjustable from 0.5-10
seconds for VA Series products. A time delay on drop-out fixed at 500ms is available
(see Page 28).
NOMINAL
VOLTAGE
NOMINAL
VOLTAGE
120V AC
110V DC
120V AC
110V DC
12V DC
24V DC
48V DC
12V DC
24V DC
48V DC
24V AC
Drop-out Voltage is fixed at 95% of the adjusted Pick-up Setting.
24V AC
Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
VOLTAGE RANGE VOLTAGE RANGE
VOLTAGE RANGE VOLTAGE RANGE*
Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
102-138V AC
102-138V AC
94-126V DC
94-126V DC
21-27V AC
10-14V DC
21-27V DC
41-55V DC
10-14V DC
21-27V DC
41-55V DC
21-27V AC
PICK-UP
PICK-UP
Adjustable Pick-Up, Fixed Drop-Out Settings *
Adjustable Pick-Up & Drop-Out Settings **
71-121V DC
DROP-OUT
77-131V AC
89-121V DC
DROP-OUT
97-131V AC
16-26V DC
32-52V DC
16-26V AC
20-26V DC
39-53V DC
20-26V AC
8-13V DC
9-13V DC
Application Data & Dimensions Page 31
PRODUCT
VAKP012D
VAKP024D
VAKP048D
PRODUCT
VAKP024A
VAKP120A
VAKP110D
NUMBER
VAP012D
VAP024D
VAP048D
NUMBER
VAP024A
VAP120A
VAP110D
DIAGRAM 20
DIAGRAM 20
8 Pin Octal
8 Pin Octal
SOCKET
WIRING/
SOCKET
70169-D
WIRING/
70169-D
1/09

Related parts for VAKP012D

VAKP012D Summary of contents

Page 1

... Pin Octal 97-131V AC VAP120A 70169-D 9-13V DC VAP012D 20-26V DC VAP024D 39-53V DC VAP048D 89-121V DC VAP110D DIAGRAM 20 DROP-OUT PRODUCT WIRING/ NUMBER SOCKET 16-26V AC VAKP024A 8 Pin Octal 77-131V AC VAKP120A 8-13V DC VAKP012D 16-26V DC VAKP024D 32-52V DC VAKP048D 71-121V DC VAKP110D DIAGRAM 20 Application Data & Dimensions Page 31 70169-D 1/09 ...

Page 2

... Operating Modes These relays can be used as either overvoltage or undervoltage relays, depending on the output contact used: Overvoltage Relay Provides protection to equipment that cannot handle excess voltages. Uses a normally closed contact (N.C.). As long as the monitored voltage remains below the maximum voltage the equipment can withstand (Pick-Up Setting), the relay remains de- energized and the N ...

Related keywords