VMP024D MACROMATIC CONTROLS, VMP024D Datasheet

VOLTAGE MONITORING RELAY, DPDT, 24VDC

VMP024D

Manufacturer Part Number
VMP024D
Description
VOLTAGE MONITORING RELAY, DPDT, 24VDC
Manufacturer
MACROMATIC CONTROLS
Series
VMr
Datasheet

Specifications of VMP024D

Contact Configuration
DPDT
Power Consumption
3VA
Supply Voltage Max
24VDC
Relay Mounting
Plug In
Control Voltage Type
DC
Relay Terminals
8 Pin Octal
Control Voltage
24VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
VOLTAGE MONITOR RELAYS
VM Series Over/Undervoltage
Fixed Time Delay on Drop-Out
12-120V Plug-in
u
u
u
u
u
u
u
28
www.macromatic.com
sales@macromatic.com
800-238-7474
Monitors AC single phase
and DC voltages
Wide range of user-adjust-
able pick-up and drop-out
settings
Fixed time delay on drop-
out of 500ms
LED indicates output relay
status
Compact plug-in case
utilizing industry standard 8
pin octal socket
10A DPDT output contacts
(with appropriate socket)
*
** Drop-out Voltage is adjustable from 75-95% of the adjusted Pick-up Setting.
Sockets & Accessories Pages 81 & 82
Over/Under Voltage Relays provide protection to equipment where either an over or
under voltage condition is potentially damaging. They are designed to operate when the
operating voltage reaches a preset value and drop-out when the operating voltage drops
to a level below the preset value.
The pick-up voltage setting is user-
adjustable from 85-115% of the
nominal voltage rating. As
standard, the VMP Series has a
drop-out voltage setting fixed at
95% of the pick-up voltage setting.
An adjustable drop-out setting of
75-95% of the pick-up setting is
available on the VMKP Series.
The relay energizes when the
monitored voltage is above the pick-up setting. The relay de-energizes when the moni-
tored voltage is below the drop-out setting for a period longer than the drop-out time
delay (T), which is a fixed 500ms for VM Series products. An adjustable time delay on
drop-out of 0.5-10 seconds is available (see Page 30).
NOMINAL
VOLTAGE
NOMINAL
VOLTAGE
110V DC
120V AC
120V AC
110V DC
12V DC
24V DC
48V DC
Drop-out Voltage is fixed at 95% of the adjusted Pick-up Setting.
12V DC
24V DC
48V DC
24V AC
24V AC
VOLTAGE RANGE VOLTAGE RANGE
VOLTAGE RANGE VOLTAGE RANGE*
102-138V AC
102-138V AC
94-126V DC
94-126V DC
10-14V DC
21-27V DC
41-55V DC
21-27V AC
10-14V DC
21-27V DC
41-55V DC
21-27V AC
PICK-UP
PICK-UP
Adjustable Pick-Up, Fixed Drop-Out Settings *
Adjustable Pick-Up & Drop-Out Settings **
Time Delay on Drop-out Fixed at 500ms
Time Delay on Drop-out Fixed at 500ms
77-131V AC
71-121V DC
DROP-OUT
97-131V AC
89-121V DC
16-26V DC
32-52V DC
DROP-OUT
16-26V AC
20-26V DC
39-52V DC
20-26V AC
8-13V DC
9-13V DC
Application Data & Dimensions Page 29
VMKP012D
VMKP024D
VMKP048D
VMKP024A
VMKP120A
VMKP110D
PRODUCT
PRODUCT
VMP024A
VMP120A
VMP012D
VMP024D
VMP048D
VMP110D
NUMBER
NUMBER
DIAGRAM 20
DIAGRAM 20
8 Pin Octal
8 Pin Octal
SOCKET
SOCKET
WIRING/
WIRING/
70169-D
70169-D
1/09

Related parts for VMP024D

VMP024D Summary of contents

Page 1

... Drop-out Voltage is adjustable from 75-95% of the adjusted Pick-up Setting. Sockets & Accessories Pages 81 & 82 DROP-OUT PRODUCT WIRING/ NUMBER SOCKET 20-26V AC VMP024A 8 Pin Octal 97-131V AC VMP120A 70169-D 9-13V DC VMP012D 20-26V DC VMP024D 39-52V DC VMP048D 89-121V DC VMP110D DIAGRAM 20 DROP-OUT PRODUCT WIRING/ NUMBER SOCKET 16-26V AC VMKP024A 8 Pin Octal 77-131V AC VMKP120A ...

Page 2

... Operating Modes These relays can be used as either overvoltage or undervoltage relays, depending on the output contact used: Overvoltage Relay Provides protection to equipment that cannot handle excess voltages. Uses a normally closed contact (N.C.). As long as the monitored voltage remains below the maximum voltage the equipment can withstand (Pick-Up Setting), the relay remains de- energized and the N ...

Related keywords