M3PRC/S/2-4W 230VAC BROYCE CONTROL, M3PRC/S/2-4W 230VAC Datasheet

no-image

M3PRC/S/2-4W 230VAC

Manufacturer Part Number
M3PRC/S/2-4W 230VAC
Description
RELAY,UNDER/OVER V/LOSS, 3PHASE, 230VAC
Manufacturer
BROYCE CONTROL
Series
4-Wirer
Datasheet

Specifications of M3PRC/S/2-4W 230VAC

Contact Configuration
DPDT
Relay Mounting
DIN Rail
Contact Current Ac Max
8A
Contact Current Dc Max
8A
Contact Voltage Ac Max
250V
Contact Voltage Dc Max
25V
External
RoHS Compliant
Rohs Compliant
Yes
• FUNCTION DIAGRAM
• INSTALLATION AND SETTING
Applying power.
Setting the unit.
Troubleshooting.
The table below shows the status of the unit during a fault condition.
• CONNECTION DIAGRAM
Type: M3PRC/S/2 & M3PRC/S/2-4W
Phase Failure, Phase Sequence, Under and Over Voltage plus Time Delay
Supply fault
Phase or Neutral (4-wire only) missing
Phases reversed (no delay)
Under or Over Voltage condition (during timing)
Under or Over Voltage condition (after timing)
Phase below 70% of Un (fixed under trip level [2])
Phase below 50% of Un
BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Connect the unit as required. The diagram below shows a typical installation, whereby the supply to
the load is being monitored by the relay. If a fault should occur (i.e. fuse blowing), the contactor is de-
energised removing the 3-phase supply to the load. The contactor only re-energises after the fault has
cleared.
Set the “over %” adjustment to maximum and the “under %” adjustment to minimum. Set the
“time delay” to minimum.
Apply power and the green “supply on” and red “relay” LED’s will illuminate, the relay will energise
and contacts 15 and 18 / 25 and 28 will close. Refer to the troubleshooting table if the unit fails to
operate correctly.
Set the “over %” and the “under %” adjustments to give the required monitoring range.
If large supply variations are anticipated, the adjustments should be set further from the nominal
voltage.
Set the “time delay” as required. (Note that the delay is only effective should the supply increase
above or drop below the set trip levels. However, if during an under voltage condition the supply
drops below the 2
de-energises).
35mm DIN rail housing
Microprocessor controlled with internal monitoring (self-checking)
Monitors own supply and detects if one or more phases exceed the set Under or Over Voltage
trip levels
M3PRC/S/2 measures phase to phase voltage and M3PRC/S/2-4W measures phase to neutral voltage
Detects incorrect phase sequence, phase loss and neutral loss (4-wire only)
Adjustments for under and over voltage trip levels
Adjustment for time delay (from an under or over voltage condition)
1 x DPDT relay output 8A
Intelligent LED indication for supply and relay status
(4-wire only) N
Fixed
Under trip [2]
Monitored
3~ Supply
Output
L1, L2
L2, L3
L3, L1
L1 (R)
L2 (Y)
L3 (B)
N*
Supply / Monitored
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely
Voltage
nd
Over trip
Hyst.
Hyst.
Under trip
Local Fuse
under voltage trip level, any set time delay is automatically cancelled and the relay
Td
Board
t
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
N*
16 18
15
Phase monitor
L3
t
Green LED
Off
Flashing
On
On
On
Off
L2
26 28
25
time delay automatically cancelled as
phase drops below 2nd trip point
L1
Contactor
tr
Red LED
Off
Off
Flashing
Off
Off
Off
*N - Neutral connection
only available on 4-wire
version
Installation work must be carried
tr
out by qualified personnel.
Phases reversed
LOAD
Relay
De-energised
De-energised
Energised for set delay (t)
De-energised
De-energised
De-energised
Td
at the user’s own risk
.
• TECHNICAL SPECIFICATION
Supply / monitoring
Frequency range:
Supply variation:
Isolation:
Rated impulse
Power consumption:
(max.)
Trip levels:
Measuring ranges:
Repeat accuracy:
Hysteresis:
Response time:
Time delay (t):
Delay from
Power on delay (Td):
Ambient temp:
Relative humidity:
Output:
Output rating:
Electrical life:
Dielectric voltage:
Rated impluse
Housing:
Weight:
Mounting option:
Terminal conductor size:
Approvals:
Options:
For other supply/monitoring voltages, please contact the sales office.
• MOUNTING DETAILS
voltage Un* (L1, L2, L3):
withstand voltage:
withstand voltage:
phase/neutral loss (tr):
surface mounting
Withdraw clips
fully when
(L1, L2, L3, N):
Insert screwdriver
Under [2]:
Over:
Under:
63.5V:
120V:
127V:
220V:
230V:
240V:
110V:
208V:
220V:
380V:
400V:
415V:
to release clips
3-wire: 110, 208, 220, 380, 400, 415V AC (phase to phase)
4-wire: 63.5, 120, 127, 220, 230, 240V AC (phase to neutral)
48 - 63Hz
70 - 130% of Un
Over voltage cat. III
4kV (1.2 / 50μS) IEC 60664
red phase: 20VA (3-wire), 13VA (4-wire)
yellow phase: 0.2VA (3-wire), 0.1VA (4-wire)
blue phase: 20VA (3-wire), 0.1VA (4-wire)
70% of Un (fixed) ±2%
75 - 95% of Un
105 - 125% of Un
Under
48 - 60V
90 - 114V
95 - 121V
165 - 209V
173 - 218V
180 - 228V
83 - 105V
156 - 197V
165 - 209V
285 - 361V
300 - 380V
311 - 394V
** measured phase to neutral
± 0.5% @ constant conditions
≈ 2% of trip level (factory set)
≈ 50 mS
0.2 - 10 sec (± 5%)
Note: actual delay (t) = adjustable delay + response time
≈ 100 mS (worst case = tr x 2)
≈ 1sec. (worst case = Td x 2)
-20 to +60°C
+95%
DPDT relay (15, 16, 18 / 25, 26, 28)
AC1
AC15
DC1
≥ 150,000 ops at rated load
2kV AC (rms) IEC 60947-1
4kV (1.2 / 50μS) IEC 60664
Orange flame retardant UL94 VO
≈ 100g
On to 35mm symmetric DIN rail to BS5584:1978
(EN50 002, DIN 46277-3) Or direct surface mounting via 2 x
M3.5 or 4BA screws using the black clips provided on the rear
of the unit.
≤ 2 x 2.5mm
Conforms to IEC. CE and
to DIN 43880
W. 35mm
Dims:
89 (excl. clips)
93 (+/- 1mm)
2
solid or stranded
Over
67 - 79V (4-wire **)
126 - 150V (4-wire **)
133 - 159V (4-wire **)
231 - 275V (4-wire **)
241 - 288V (4-wire **)
252 - 300V (4-wire **)
116 - 138V (3-wire)
218 - 260V (3-wire)
231 - 275V (3-wire)
399 - 475V (3-wire)
420 - 500V (3-wire)
436 - 519V (3-wire)
250V 8A (2000VA)
250V 3A
25V 8A (200W)
45
Compliant.
Supply / monitoring
voltage when ordering
Terminal Protection to IP20
Please state
49 59
M3PRCS2-3-A