TR-61828 MACROMATIC CONTROLS, TR-61828 Datasheet - Page 4

TIME DELAY RELAY, DPDT, 120MIN, 24VAC/DC

TR-61828

Manufacturer Part Number
TR-61828
Description
TIME DELAY RELAY, DPDT, 120MIN, 24VAC/DC
Manufacturer
MACROMATIC CONTROLS
Datasheet

Specifications of TR-61828

Contact Configuration
DPDT
Nom Input Voltage
24V
Delay Time Range
0.1s To 120min
Timing Adjustment
Knob
Relay Mounting
Plug In
Relay Terminals
11 Pin Octal
Mounting Type
Plug In
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Voltage Tolerance:
AC Operation:
DC Operation:
Load (Burden):
2 VA
Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable):
Repeat Accuracy (constant voltage and temperature):
> 2 Seconds Delay
0.1 - 2 Seconds Delay
Reset Time:
On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 Seconds
Off Delay/Single Shot/Watchdog/
Triggered Delayed Interval: 0.04 Seconds
Start-up Time:
(Time from when power is applied until unit is timing)
120 & 240V units
12, 24 & 48V units
Maintain Function Time:
(Time unit continues to time after power is removed)
0.01 Seconds for all units
Temperature:
12-120V Input Voltage: -28
240V Input Voltage:
Dimensions
Application Data
1/09
+10/-15% of nominal at 50/60 Hz.
+10/-15% of nominal.
0.05 Seconds
0.08 Seconds
-28
(60)
2.4
+0.1%
+2%
o
o
to 65
to 50
+0%, -50%
o
o
C (-18
C (-18
o
o
to 150
to 122
(43)
1.7
o
o
F)
F)
File #E109466
Insulation Voltage:
2,000 volts
Output Contacts:
DPDT 10A @ 240V AC/30V DC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
B300 & R300; AC15 & DC13
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Compatibility:
On all units triggered by input voltage or by a control switch,
do not use a solid state switch to initiate the timing sequence-
problems with leakage current could occur. On all units with a
power trigger, do not use a solid state switch with leakage
current exceeding 0.5ma. Contact Macromatic Controls for
additional information.
Triggering Off Delay, Single Shot or Watchdog Units:
Timing sequence must be initiated only after input voltage is
applied to unit. Minimum required trigger switch closure time
is 0.1 seconds.
Approvals:
TIME DELAY RELAYS
Time Ranger
File #LR45565
(74)
2.9
Application Data & Dimensions
(89)
3.5
Multi-Range Plug-in
EN60947-1, EN60947-5-1
EMC Directives
Low Voltage &
TM
Programmable
Inches (Millimeters)
All Dimensions in
File #E109466
appropriate
socket
with
57